Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
144
Environmental data 787310 787313
Rated insulation voltage 250 V 250 V
Rated impulse withstand voltage 4 kV 4 kV
Protection type
Mounting area (e.g. control cab-
inet) IP54 IP54
Housing IP40 IP40
Terminals IP20 IP20
Mechanical data 787310 787313
Mounting position Any Any
Mechanical life 10,000,000 cycles 10,000,000 cycles
Material
Bottom PPO UL 94 V0 PPO UL 94 V0
Front ABS UL 94 V0 ABS UL 94 V0
Top PPO UL 94 V0 PPO UL 94 V0
Connection type Spring-loaded terminal Spring-loaded terminal
Mounting type plug-in plug-in
Conductor cross section with
spring-loaded terminals: Flexible
with/without crimp connector 0,2 - 1,5 mm², 24 - 16 AWG 0,2 - 1,5 mm², 24 - 16 AWG
Spring-loaded terminals: Terminal
points per connection 2 2
Stripping length with spring-loaded
terminals 8 mm 8 mm
Dimensions
Height 101 mm 101 mm
Width 45 mm 45 mm
Depth 121 mm 121 mm
Weight 270 g 310 g
Where standards are undated, the 2014-07 latest editions shall apply.
Safety characteristic data
Operating
Mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
PL e Cat. 4 SIL CL 3 2,31E-09 SIL 3 2,03E-06 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.