Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X2.8P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
99
Relay outputs 777301 777302
External contact fuse protection,
auxiliary contacts
Max. melting integral 160 A²s 66 A²s
Blow-out fuse, quick 10 A 6 A
Blow-out fuse, slow 6 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
777301 777302
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 4 A 6 A
Conv. therm. current with 3 con-
tacts 3,5 A 4,5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 5 A 4,5 A
Times 777301 777302
Switch-on delay
With automatic start typ. 250 ms 340 ms
With automatic start max. 450 ms 400 ms
With automatic start after power
on typ. 250 ms 600 ms
With automatic start after power
on max. 450 ms 800 ms
With manual start typ. 125 ms 180 ms
With manual start max. 450 ms 400 ms