Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
142
Relay outputs 787310 787313
External contact fuse protection,
auxiliary contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
787310 787313
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 7 A 7 A
Conv. therm. current with 3 con-
tacts 6 A 6 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 7 A
Conv. therm. current with 3 con-
tacts 7 A 6 A
Times 787310 787313
Switch-on delay
With automatic start typ. 250 ms 330 ms
With automatic start max. 500 ms 450 ms
With automatic start after power
on typ. 280 ms 750 ms
With automatic start after power
on max. 550 ms 1.000 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 50 ms 50 ms