N disconnect terminal block-PTN 6-3213967
Technical data
General
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Oscillation, broadband noise test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
30 g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Shock test result
Test passed
Temperature index, insulating material (DIN EN 60216-1 (VDE
0304-21))
130 °C
Static insulating material application in cold
-60 °C
Dimensions
Width
8.2 mm
Length
66.3 mm
Height
48.50 mm
Height NS 35/7,5
50 mm
Height NS 35/15
57.5 mm
Connection data
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
10 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
8
Conductor cross section stranded min.
0.5 mm²
Conductor cross section stranded max.
6 mm²
Min. AWG conductor cross section, stranded
20
Max. AWG conductor cross section, stranded
10
Conductor cross section stranded, with ferrule without plastic
sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve max.
6 mm²
Conductor cross section stranded, with ferrule with plastic
sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule with plastic
sleeve max.
6 mm²
2 conductors with same cross section, stranded, TWIN
ferrules with plastic sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, TWIN
ferrules with plastic sleeve, max.
1.5 mm²
Connection method
Push-in connection
Stripping length
12 mm
Internal cylindrical gage
A5