Technical data
General
Test frequency
f
1
= 5 Hz to f
2
= 150 Hz
ASD level
1.857 (m/s
2
)
2
/Hz
Acceleration
0.8 g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Oscillation, broadband noise test result
Test passed
Test specification, shock test
DIN EN 50155 (VDE 0115-200):2008-03
Shock form
Half-sine
Acceleration
5 g
Shock duration
30 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Shock test result
Test passed
Temperature index, insulating material (DIN EN 60216-1 (VDE
0304-21))
130 °C
Static insulating material application in cold
-60 °C
Dimensions
Width
3.5 mm
Length
45.8 mm
Height NS 35/7,5
32 mm
Height NS 35/15
39.5 mm
Connection data
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
14
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Min. AWG conductor cross section, stranded
26
Max. AWG conductor cross section, stranded
14
Conductor cross section stranded, with ferrule without plastic
sleeve min.
0.14 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve max.
1.5 mm²
Conductor cross section stranded, with ferrule with plastic
sleeve min.
0.14 mm²
Conductor cross section stranded, with ferrule with plastic
sleeve max.
1 mm²
Connection method
Push-in / plug connection
Stripping length
8 mm
Internal cylindrical gage
A1 / B1