Datasheet


Technical data
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
30 400
2
) 0.5 - 10 20 - 8 30 400
IEC 60947-7-1
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 400
2
) 300 - - 400
Nominal current / cross section [A] / [mm²] 24
1
) / 6 10 - - 24
Rated cross section [mm²]6--- 6--- 6--- 6---
Cross section range AWG 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 20 - 14 - - -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 - 0.5 - 2.5 - -
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - -
Plug-in connection cross sections [mm²] 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 - - - -
General data
Stripping length [mm] 12
Tightening torque for wall fastening [Nm] 0.8 - 1
Panel thickness [mm] 1 - 4
Tightening torque: test socket screw [Nm] -
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Test terminal strip, wall mounting gray PTWE 6-2/A14 3069439 1
Test terminal strip, DIN rail mounting gray PTRE 6-2/A14 3069452 1
Test plug, with twist grip, A14 coding gray
B14 coding gray
C14 coding gray
Test plug, with standard grip, A14 coding gray
B14 coding gray
C14 coding gray
Test plug, 1-pos., with cover red
Blind plug, sealable, A14 coding gray
B14 coding gray
C14 coding gray
542
PHOENIX CONTACT
Test terminal strip, with push-in
connection, wall or DIN rail mounting
The VDEA14 version is suitable as a
plug-in test system for three-stage
automatic frequency discharge, as zero-
power comparison protection, and as stator
and rotor ground fault protection.
The VDEB14 version is suitable as a
plug-in test system in overcurrent
directional protection, distance protection
for high and medium voltage, as well as
voltage regulation.
The VDEC14 version is suitable as a
plug-in test system in overcurrent time
protection, unbalanced load protection, and
stator ground fault protection for busbar
operation.
The test plugs are assembled with
jumpers and contact tab lengths
according to the circuit diagram
A transparent covering hood protects the
jumpers. The covering hood can only be
removed by dismantling the test plug
All VDE-specified 7, 14, and 19-pos.
versions are supplied with exclusive
coding for the matching test plug and
blind plug
The components are supplied pre-marked
according to the VDE Directive
Test signals can be connected with touch-
proof safety test leads (CATIII and
IV/1000V according to EN61010-031)
The test plugs are equipped with two gray
test sockets per position, for further
color versions, see the range of
accessories
Blind plug
The FBP-2.. blind plug is an optional
protective cover for the test terminal strip
and is characterized by:
Secure, sealable latching on the test
terminal strip
Can only be removed by means of two-
hand operation
Large marking option
Blind plug, 14-pos., VDE coded
Sector-specific solutions
Solutions for energy technology
Notes:
To create panel cutouts, see phoenixcontact.net/products.
1
) Derating curve available on request.
2
) Rated surge voltage of 5 kV.
6 (10) mm², 30A, test terminal strip, VDE
coded type A14