For further information and full technical data, visit phoenixcontact.net/products
Technical data
Dimensions Width Length Height NS 35/7,5
[mm] 22.5 64.5 54
Dimensions Width Length Height NS 32
[mm] 22.5 64.5 59
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
57 110
1
) 0.5 - 10 26-8
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 110
1
) 250 - -
Nominal current / cross section [A] / [mm²] 41 / 6 50 / - - -
Rated cross section [mm²] 6 - - -
Cross section range AWG 20 - 8 26-8 - -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 10 0.5 - 6 0.5 - 10 0.5 - 4
2 conductors (of the same type) [mm²] 0.5 - 6 0.5 - 6 0.5 - 6 -
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 4
General data
Stripping length [mm] 12
Screw thread M4
Tightening torque [Nm] 1.2 - 1.5
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Basic disconnect terminal block, for mounting
on NS32..., NS35... or NS35/15-2,3 for 110–
250VAC/DC, current: 0.5–1mA
gray GTF 76/230 3121012 10
Basic disconnect terminal block, for mounting
on NS32..., NS35... or NS35/15-2,3 for 24–
48VAC/DC, current: 3.5–8mA
gray GTF 76/ 48 3121025 10
Accessories
Screwdriver SZS 1,0X4,0 VDE 1205066 10
Lateral groove marking ZB 10 (see Catalog 5)
External
operating indicator
Yellow
operating indicator
Red
ground fault indicator
Grounded operating mode
External
operating indicator
Yellow
operating indicator
Red
ground fault indicator
Ground fault
437
PHOENIX CONTACT
EN 60204-1/VDE 0113-1 "Electrical
Equipment of Industrial Machines", Section
9.4.3.1 states:
"Ground faults in a control circuit may
not lead to an unintentional start-up, to
potentially dangerous movements or
prevent the stopping of a machine."
The ground disconnect terminal block
GTF76 conveniently solves this problem
When the disconnect slide is closed,
switch position "on", the yellow light
signals grounded normal operation
Once the disconnect slide has been
opened to the "off" position, the red light
indicates whether there is a ground fault
in the control circuit
Note:
Asymmetries in the cable isolation mean
that the red display may easily light up
even when there is no ground fault if the
disconnect slide is open. This has no
impact on functionality and does not
affect the protective measure demanded
in the VDE requirements
Attention!
During isolation testing according to
EN60204–1/VDE0113–1, the GTF76
should be disconnected or bridged as
otherwise the LED display will be
destroyed or a short circuit will occur
Notes:
1
) 250V for GTF76/230
GTF 76 ground disconnect terminal
block
Terminal blocks
UK universal terminal blocks
6 (10) mm², 57 A, ground disconnect terminal
block