Datasheet


Technical data
1
) Technical data
1
)
Dimensions Width Length Height Width Length Height
[mm] 78 29.1 34.3 86.7 56.4 34.3
Max. electrical data I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL) I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL)
15 320 0.5 - 2.5 - 15 320 0.14 - 6 -
Rated data IEC UL / CUL CSA Ex IEC UL / CUL CSA Ex
Rated voltage [V] 320 - - - 320 - - -
Nominal current / cross section [A] / [mm²] 15 - - - 15 - - -
Rated cross section [mm²] 2.5 6
Cross section range AWG 20 - 14 - - - 26 - 10 - - -
Connection capacity solid stranded Ferrule
without/with plastic sleeve
solid stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 2.5 0.5 - 2.5 - - 0.14 - 6 0.14 - 6 0.25 - 4 0.25 - 4
2 conductors (of the same type) [mm²] - - - - 0.14 - 1.5 0.14 - 1.5 0.25 - 1.5 -
General data
Stripping length [mm] - 8 - 9
Ordering data Ordering data
Description
No. of
pos.
Color Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
PCB connector, with screw flange
covers
8 gray FC 4-PCB/8 3208694 10
10 gray FC 4-PCB/10 3208736 10
Short-circuit plug, for four current
transformers
8 gray UP 4-4CT 3208720 10
Connector, for four voltage
transducers
8 gray UP 4-4VT 3208721 10
Short-circuit plug, for four current
transformers, bolt connection
10 gray BP 4-5CT 3208733 10
Connector, for four voltage
transducers, bolt connection
10 gray BP 4-5VT 3208734 10
246
PHOENIX CONTACT
Terminal blocks - CLIPLINE complete
4 mm COMBI UT plug-in connection solutions
Direct connection of current
transformers and voltage transducers,
e.g.,to a protective relay for medium-
voltage switchgear
UP 4...CT and BP 4...CT connectors
contain a short-circuit element. When
removing the connector from the device,
a leading short circuit of the connected
current transformer is carried out.
Notes:
1
) For additional accessories and technical data, see page 240.
new
new
Connectors