Datasheet
Technical data
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
30 400
2
) 0.5 - 10 20 - 8 30 400
IEC 60947-7-1
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 400
2
) 300 - - 400
Nominal current / cross section [A] / [mm²] 24
1
) / 6 10 - - 24
Rated cross section [mm²]6--- 6--- 6--- 6---
Cross section range AWG 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 24 - 8 24 - 8 - - 24 - 8 24 - 8 - -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.2 - 10 0.2 - 10 0.25 - 6 0.25 - 6 0.2 - 10 0.2 - 10 0.25
2 conductors (of the same type) [mm²] - - - - - - - - 0.2 - 2.
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - 0.5 - 2.5 - - - 0.5 - 2.5
Plug-in connection cross sections [mm²] 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 - - - - - - - -
General data
Stripping length [mm] 12
Tightening torque for wall fastening [Nm] 0.8 - 1
Panel thickness [mm] 1 - 4
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Test terminal strip, 4-pos. gray PTWE 6-2/4 3069827 1
5-pos. gray PTWE 6-2/5 3069828 1
6-pos. gray PTWE 6-2/6 3069829 1
7-pos. gray PTWE 6-2/7 3069830 1
8-pos. gray PTWE 6-2/8 3069831 1
9-pos. gray PTWE 6-2/9 3069832 1
10-pos. gray PTWE 6-2/10 3069833 1
11-pos. gray PTWE 6-2/11 3069834 1
12-pos. gray PTWE 6-2/12 3069835 1
13-pos. gray PTWE 6-2/13 3069836 1
14 pos. gray PTWE 6-2/14 3069837 1
15-pos. gray PTWE 6-2/15 3069838 1
16-pos. gray PTWE 6-2/16 3069839 1
17-pos. gray PTWE 6-2/17 3069840 1
18-pos. gray PTWE 6-2/18 3069841 1
19 pos. gray PTWE 6-2/19 3069842 1
20 pos. gray PTWE 6-2/20 3069843 1
21 pos. gray PTWE 6-2/21 3069844 1
22 pos. gray PTWE 6-2/22 3069845 1
23-pos. gray PTWE 6-2/23 3069846 1
24-pos. gray PTWE 6-2/24 3069847 1
25 pos. gray PTWE 6-2/25 3069848 1
Accessories
Cover profile, supply length 1m transparent AP RSC-T 3059139 10
Cover profile holder, can be snapped on and
sealed
gray APH-UTWE 6-2 3069057 10
Cover profile, supply length 1m transparent
End bracket, for AP-ME cover profile gray
Holder, for AP-ME cover profile gray
Screwdriver SF-SL 0,8X4,0-100 1212551 10
Lateral groove marking UC-TM 8, UCT-TM 8, ZB 8 or TMT(EX9,5)R
(see Catalog 5)
532
PHOENIX CONTACT
Test terminal strip, with push-in
connection or screw connection
Notes:
To create panel cutouts, see phoenixcontact.net/products.
For further jumpers, see page 538.
1
) Derating curve available on request.
2
) Rated surge voltage: 4 kV.
The modular FAME measuring transducer
test system enables all transformer testing
tasks to be carried out quickly and safely.
The transformer is short-circuited and the
test device is looped in automatically when
inserted.
– The test terminal strips can be used
universally for current and voltage
transducers
– The test terminal strip can be mounted
on the control cabinet door or on the
DIN rail
– Signal and status messages can be wired in
combination in a test terminal strip
– The correct switching sequence when
removing the test plug is ensured by a
locking device and a mechanical drive in
the twist grip
– All test signals can be connected with
touch-proof safety test leads (CATIII and
CATIV/1000V according to EN61010-
031)
– All versions listed can be equipped with
coding for the matching test plug
– Star points of the current transformer
can easily be created in the test terminal
strip on the rear by means of FBS jumpers
– You can find corresponding accessories
from page 537
Sector-specific solutions
Solutions for energy technology
6 (10) mm², 30 A, 4...25-pos. test terminal
strip, for wall mounting, push-in connection