Datasheet


Technical data
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
30 400
2
) 0.5 - 10 20 - 8 30 400
IEC 60947-7-1
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 400
2
) 300 - - 400
Nominal current / cross section [A] / [mm²] 24
1
) / 6 10 - - 24
Rated cross section [mm²]6--- 6--- 6--- 6---
Cross section range AWG 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 24 - 8 24 - 8 - - 24 - 8 24 - 8 - -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.2 - 10 0.2 - 10 0.25 - 6 0.25 - 6 0.2 - 10 0.2 - 10 0.25
2 conductors (of the same type) [mm²] - - - - - - - - 0.2 - 2.
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - 0.5 - 2.5 - - - 0.5 - 2.5
Plug-in connection cross sections [mm²] 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 - - - - - - - -
General data
Stripping length [mm] 12
Tightening torque for wall fastening [Nm] 0.8 - 1
Panel thickness [mm] 1 - 4
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Test terminal strip, 4-pos. gray PTWE 6-2/4 3069827 1
5-pos. gray PTWE 6-2/5 3069828 1
6-pos. gray PTWE 6-2/6 3069829 1
7-pos. gray PTWE 6-2/7 3069830 1
8-pos. gray PTWE 6-2/8 3069831 1
9-pos. gray PTWE 6-2/9 3069832 1
10-pos. gray PTWE 6-2/10 3069833 1
11-pos. gray PTWE 6-2/11 3069834 1
12-pos. gray PTWE 6-2/12 3069835 1
13-pos. gray PTWE 6-2/13 3069836 1
14 pos. gray PTWE 6-2/14 3069837 1
15-pos. gray PTWE 6-2/15 3069838 1
16-pos. gray PTWE 6-2/16 3069839 1
17-pos. gray PTWE 6-2/17 3069840 1
18-pos. gray PTWE 6-2/18 3069841 1
19 pos. gray PTWE 6-2/19 3069842 1
20 pos. gray PTWE 6-2/20 3069843 1
21 pos. gray PTWE 6-2/21 3069844 1
22 pos. gray PTWE 6-2/22 3069845 1
23-pos. gray PTWE 6-2/23 3069846 1
24-pos. gray PTWE 6-2/24 3069847 1
25 pos. gray PTWE 6-2/25 3069848 1
Accessories
Cover profile, supply length 1m transparent AP RSC-T 3059139 10
Cover profile holder, can be snapped on and
sealed
gray APH-UTWE 6-2 3069057 10
Cover profile, supply length 1m transparent
End bracket, for AP-ME cover profile gray
Holder, for AP-ME cover profile gray
Screwdriver SF-SL 0,8X4,0-100 1212551 10
Lateral groove marking UC-TM 8, UCT-TM 8, ZB 8 or TMT(EX9,5)R
(see Catalog 5)
532
PHOENIX CONTACT
Test terminal strip, with push-in
connection or screw connection
Notes:
To create panel cutouts, see phoenixcontact.net/products.
For further jumpers, see page 538.
1
) Derating curve available on request.
2
) Rated surge voltage: 4 kV.
The modular FAME measuring transducer
test system enables all transformer testing
tasks to be carried out quickly and safely.
The transformer is short-circuited and the
test device is looped in automatically when
inserted.
The test terminal strips can be used
universally for current and voltage
transducers
The test terminal strip can be mounted
on the control cabinet door or on the
DIN rail
Signal and status messages can be wired in
combination in a test terminal strip
The correct switching sequence when
removing the test plug is ensured by a
locking device and a mechanical drive in
the twist grip
All test signals can be connected with
touch-proof safety test leads (CATIII and
CATIV/1000V according to EN61010-
031)
All versions listed can be equipped with
coding for the matching test plug
Star points of the current transformer
can easily be created in the test terminal
strip on the rear by means of FBS jumpers
You can find corresponding accessories
from page 537
Sector-specific solutions
Solutions for energy technology
6 (10) mm², 30 A, 4...25-pos. test terminal
strip, for wall mounting, push-in connection