Datasheet


Technical data
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
30 400
2
) 0.5 - 10 20 - 8 30 400
IEC 60947-7-1
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 400
2
) 300 - - 400
Nominal current / cross section [A] / [mm²] 24
1
) / 6 10 - - 24
Rated cross section [mm²]6--- 6--- 6--- 6---
Cross section range AWG 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 20 - 8 20 - 8 - - 20 - 14 - - -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 0.5 - 10 0.5 - 6 0.5 - 6 0.5 - 6 - 0.5 - 2.5 - -
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - 0.5 - 1.5 - - - -
Plug-in connection cross sections [mm²] 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 1 - 10 - 1 - 6 1 - 6 - - - -
General data
Stripping length [mm] 12
Tightening torque for wall fastening [Nm] 0.8 - 1
Panel thickness [mm] 1 - 4
Tightening torque: test socket screw [Nm] -
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Test terminal strip, wall mounting gray PTWE 6-2/F19 3069445 1
Test terminal strip, DIN rail mounting gray PTRE 6-2/F19 3069458 1
Test plug, with twist grip, F19 coding gray
G19 coding gray
H19 coding gray
Test plug, with standard grip, F19 coding gray
G19 coding gray
H19 coding gray
Test plug, 1-pos., with cover red
Blind plug, sealable, F19 coding gray
G19 coding gray
H19 coding gray
546
PHOENIX CONTACT
Test terminal strip, with push-in
connection, wall or DIN rail mounting
The VDEF19 version is suitable as a
plug-in test system in electromechanical
differential protection for transformers,
generators, motors, and cables.
The VDEG19 version is suitable as a
plug-in test system in digital differential
protection for transformers.
The VDEH19 version is suitable as a
plug-in test system in overcurrent
directional protection and distance
protection as system protection.
The test plugs are assembled with
jumpers and contact tab lengths
according to the circuit diagram
A transparent covering hood protects the
jumpers. The covering hood can only be
removed by dismantling the test plug
All VDE-specified 7, 14, and 19-pos.
versions are supplied with exclusive
coding for the matching test plug and
blind plug
The components are supplied pre-marked
according to the VDE Directive
Test signals can be connected with touch-
proof safety test leads (CATIII and
IV/1000V according to EN61010-031)
The test plugs are equipped with two gray
test sockets per position, for further
color versions, see the range of
accessories
Blind plug
The FBP-2.. blind plug is an optional
protective cover for the test terminal strip
and is characterized by:
Secure, sealable latching on the test
terminal strip
Can only be removed by means of two-
hand operation
Large marking option
Blind plug, 19-pos., VDE coded
Sector-specific solutions
Solutions for energy technology
Notes:
To create panel cutouts, see phoenixcontact.net/products.
1
) Derating curve available on request.
2
) Rated surge voltage of 5 kV.
6 (10) mm², 30A, test terminal strip, VDE
coded type F19