Datasheet

Technical data
1
) Technical data
1
)
Dimensions Width Length Height Width Length Height
[mm] 6.2 92.7 88.9 (NS 35/7,5) 6.2 92.7 88.9 (NS 35/7,5)
Max. electrical data I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL) I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL)
36
3
) 500
3
) 0.14 - 6 26-10 36
3
) 500
3
) 0.14 - 6 26-10
Max. bridge current [A] 32 (FBS) / 24 (FBSR) 32 (FBS) / 24 (FBSR)
Rated data IEC UL / CUL CSA Ex IEC UL / CUL CSA Ex
Rated voltage [V] 500
3
) 300 - - 500
3
) 300 - -
Nominal current / cross section [A] / [mm²] 28 / 4 16 - - 28 / 4 16 - -
Nominal current / cross section [A] / [mm²] 6.3
4
) / 1 (disconnect level) 6.3
4
) / 1 (disconnect level)
Ordering data Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
Fuse terminal block black UT 4-L/HESI (5X20) 3214325 50
black UT 4-PE/L/HESI (5X20) 3214320 50
With light indicator for 12 - 30 V DC
2
) black UT 4-PE/L/HESILED 24 (5X20) 3214321 50
for 30 – 60VAC/DC
2
) black UT 4-PE/L/HESILED 60 (5X20) 3214322 50
for 110 – 250VAC/DC
2
) black UT 4-PE/L/HESILED 250 (5X20) 3214323 50
Terminal blocks - CLIPLINE complete
4 mm UT... screw connection terminal blocks
36 A, multi-level terminal block, safety lever 36 A, multi-level terminal block, safety lever
with LED display, PE foot
Ex:
Ex:
①①
Fuse terminal blocks and lever-type
disconnect terminal blocks of the
same shape
Notes:
1
) For additional accessories and technical data, see page 40.
2
) If the fuse is faulty, the downstream circuit is not off load.
3
) For max. power dissipation, see page 616.
4
) The current is determined by the fuse used.
For lever marking, please use marking material with a 5.2 mm
pitch.
For information on installation and using accessories for Ex
applications, see page 602.
Technical data
1
) Technical data
1
)
Dimensions Width Length Height Width Length Height
[mm] 6.2 92.7 88.9 (NS 35/7,5) 6.2 92.7 61.7 (NS 35/7,5)
Max. electrical data I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL) I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL)
36 500 0.14 - 6 26-10 36 500 0.14 - 6 -
Max. bridge current [A] 32 (FBS) / 24 (FBSR) 32 (FBS) / 24 (FBSR)
Rated data IEC UL / CUL CSA Ex IEC UL / CUL CSA Ex
Rated voltage [V] 500 300 - - 500 - - -
Nominal current / cross section [A] / [mm²] 28 / 4 16 - - 28 / 4 - - -
Nominal current / cross section [A] / [mm²] 20 / 1 (disconnect level) 20
2
) / 2.5 (disconnect level)
Ordering data Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
Terminal block black UT 4-PE/L/HEDI 3214324 50
gray UT 4-PE/L/TG 3214365 50
Knife disconnect terminal block gray UT 4-PE/L/MT 3214364 50
44
PHOENIX CONTACT
36 A, multi-level lever-type disconnect
terminal block, PE foot, same shape
36 A, multi-level terminal block with
disconnect zone, PE foot

①①
Fuse terminal blocks and lever-type
disconnect terminal blocks of the
same shape
Notes:
1
) For additional accessories and technical data, see page 40.
2
) Current and voltage are determined by the plug used.
For lever marking, please use marking material with a 5.2 mm
pitch.