Datasheet
https://www.phoenixcontact.com/us/produkte/2989200
Nov 14, 20133/18
Switch-FL SWITCH GHS 12G/8-2989200
Technical data
Function
Redundancy
Spanning Tree 802.1d, Rapid Spanning Tree 802.1w, Fast Ring
Detection, Media Redundancy Protocol (MRP) as per IEC62439
Status and diagnostic indicators
Large operator display (contains IP address and other
parameters), 2 status LEDs per Ethernet port: LINK and selection
of Status Activity, 100, full duplex, supply voltage U
S1
and U
S2
(redundant supply voltage), and FAIL
Network expansion parameters
Cascading depth
Network, linear, and star structure: any
Maximum conductor length ((twisted pair)
100 m
Supply voltage
Supply voltage
24 V DC
Residual ripple
3.6 V
PP
(within the permitted voltage range)
Supply voltage range
18.5 V DC ... 30.2 V DC
Typical current consumption
800 mA (Up to 2.7 A, depends on the configuration)
Max. current consumption
2.7 A
Mechanical tests
Type of test
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Test result
Operation: 25 g, 11 ms duration, semi-sinusoidal shock impulse
Type of test
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Test result
Storage/Transport: 50 g, 11 ms duration, semi-sinusoidal shock
impulse
Type of test
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Test result
Operation/Storage/Transport: 5 g, 150 Hz, Criterion 3
Type of test
Free fall in acc. with IEC 60068-2-32
Test result
1 m
Conformity with EMC directives
Test standard
IEC 61000-4-2 (ESD)
Test standard
IEC 61000-4-3 (immunity to radiated interference)
Test result
Criterion A, 10V/m
Test standard
IEC 61000-4-4 (burst)
Test standard
IEC 61000-4-5 (surge)
Test result
Criterion B
Test standard
IEC 61000-4-6 (immunity to conducted interference)
Test standard
EN 55022 (emitted interference)
Test result
Class A
General
Mounting type
DIN rail
Type AX
Stand-alone
Weight
2700 g
Material base plate
Die-cast aluminum, corrosion-resistant
Noise emission
EN 61000-6-3/-4