Datasheet

https://www.phoenixcontact.com/us/produkte/2985974
Nov 14, 20132/5
Proxy-FL NP PND-4TX IB-2985974
Technical data
Ambient conditions
Air pressure (operation)
80 kPa ... 108 kPa (2000 above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (3000 above sea level)
Interfaces
Interface 1
Ethernet
No. of ports
4
Connection method
RJ45 socket
Transmission speed
10/100 MBit/s
Transmission length
100 m
Interface 2
INTERBUS (Master)
No. of ports
1
Connection method
9-pos. D-SUB socket
PROFINET IO
Device function
PROFINET-Proxy
Specification
PROFINET RT, spec. 3.2
Update rate
min. 1 ms
Function
Status and diagnostic indicators
7-segment display/ diagnostics LEDs
Number of supported devices
max. 512 (Depending on the control class and data direction)
Amount of process data
512 words
Number of devices with parameter channel
max. 126 (512 words)
Supply voltage
Supply voltage
24 V DC
Residual ripple
3.6 V
PP
(within the permitted voltage range)
Supply voltage range
18.5 V DC ... 30.2 V DC
Typical current consumption
typ. 350 mA
Conformity with EMC directives
Developed in acc. with standard
IEC 61000-6.2
Test standard
IEC 61000-4-2 (ESD)
Test result
Criterion B
Test standard
IEC 61000-4-3 (immunity to radiated interference)
Test result
Criterion A
Test standard
IEC 61000-4-4 (burst)
Test result
Criterion B
Test standard
IEC 61000-4-5 (surge)
Test result
Criterion B
Test standard
IEC 61000-4-6 (immunity to conducted interference)
Test result
Criterion A
Test standard
EN 55011 (emitted interference)
Test result
Class A