Solid-state relay module-PLC-OSC- 60DC/300DC/ 1-2980681
Technical data
Input data
Input voltage range
48 V DC ... 60 V DC
Switching threshold "0" signal in reference to U
N
≤ 0.4
Switching threshold "1" signal in reference to U
N
≥ 0.8
Typical input current at U
N
5 mA
Typical response time
0.3 ms
Typical turn-off time
0.7 ms
Operating voltage display
Yellow LED
Type of protection
Protection against polarity reversal
Type of protection
Surge protection
Protective circuit/component
Polarity protection diode
Protective circuit/component
Varistor
Transmission frequency
50 Hz
Output data
Name
Output data
Output voltage range
12 V DC ... 300 V DC (Partition plate PLC-ATP must be installed
for voltages larger than 250 V (L1, L2, L3) between identical
terminal points in adjacent modules. Potential bridging is then
carried out with FBST 8-PLC... or ...FBST 500...)
Limiting continuous current
1 A (see derating curve)
Voltage drop at max. limiting continuous current
< 500 mV
Type of protection
Protection against polarity reversal
Type of protection
Surge protection
Protective circuit/component
Polarity protection diode
Protective circuit/component
Varistor
Connection data
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
14
General
Mounting position
Any
Assembly instructions
In rows with zero spacing
Operating mode
100% operating factor
Inflammability class according to UL 94
V0
Name
Standards/regulations
Standards/regulations
IEC 60664