Datasheet

https://www.phoenixcontact.com/us/produkte/2941714
Nov 9, 20132/5
Load relay-ELR 3/ 9-500-2941714
Technical data
Input data
Typical input current at U
N
16 mA
Switching threshold "0" signal in reference to U
N
> 0.8
Switching threshold "1" signal in reference to U
N
< 0.3
Reaction time in normal load operation
20 ms
Transmission frequency
1 Hz (At cos φ = 0.5)
Output data
Output name
AC output
Nominal output voltage
500 V AC
Nominal output voltage range
110 V AC ... 550 V AC
Periodic peak reverse voltage
1200 V
Mains frequency
50 Hz
Mains frequency
60 Hz
Load current
9 A (see derating curve)
Leakage current
typ. 7 mA
Residual voltage
typ. 1.5 V
Surge current
230 A (tp = 10 ms, at 25 °C)
Type of protection
RC element
Protective circuit/component
RC element
Type of protection
Surge protection
Surge voltage protection
> 750 V
Connection data
Connection method
Screw connection
Stripping length
8 mm
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
10
Screw thread
M3
General
Test voltage input/output
2.5 kV
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with > 20 mm spacing
Operating mode
100% operating factor
Name
Air and creepage distances between the power circuits
Standards/regulations
EN 50178
Standards/regulations
Basic insulation
Name
Power station requirements
Name
EMC regulations