Data Sheet
https://www.phoenixcontact.com/us/products/2905026
May 3, 20172/12
Signal duplicator-MINI MCR-2-UNI-UI-2UI-2905026
Technical data
Input data
Current input signal
4 mA ... 20 mA (via DIP switch)
Current input signal
0 mA ... 10 mA (via DIP switch)
Current input signal
20 mA ... 0 mA (via DIP switch)
Current input signal
0 mA ... 24 mA (Can be set via software)
Max. input voltage
12 V
Max. input current
24 mA
Input resistance of voltage input
> 120 kΩ
Input resistance current input
approx. 50 Ω (+ 0.7 V for test diode)
Output data
Number of outputs
2
Voltage output signal
0 V ... 10 V (via DIP switch)
Voltage output signal
2 V ... 10 V (via DIP switch)
Voltage output signal
0 V ... 5 V (via DIP switch)
Voltage output signal
1 V ... 5 V (via DIP switch)
Voltage output signal
0 V ... 10.5 V (Can be set via software)
Current output signal
0 mA ... 20 mA (via DIP switch)
Current output signal
4 mA ... 20 mA (via DIP switch)
Current output signal
0 mA ... 10 mA (via DIP switch)
Current output signal
20 mA ... 0 mA (via DIP switch)
Current output signal
0 mA ... 21 mA (Can be set via software)
Max. output voltage
approx. 12.3 V
Max. output current
24.6 mA
Short-circuit current
≤ 25 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (per channel)
Ripple
< 20 mV
PP
(at 600 Ω)
Ripple
< 20 mV
PP
(at 600 Ω)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according
to EN60715))
Typical current consumption
55 mA (24 V DC)
Typical current consumption
110 mA (12 V DC)
Power consumption
1.5 W (at I
OUT
= 20 mA, 9.6 V DC, 600 Ω load)
Connection data
Connection method
Screw connection
Single conductor/terminal point, solid, with ferrule, min.
0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.
1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.
0.2 mm²