Power supply unit-QUINT4-PS/3AC/24DC/10-2904621
Technical data
Standards and Regulations
Voltage 10 V (Test Level 3)
Conducted noise emission EN 55016 EN61000-6-4 (Class A)
Standards/regulations EN 61000-4-8
EN 61000-4-11
EN 61000-4-9
EN 61000-4-12
EN 61000-4-16
EN 61000-4-18
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC60950-1/VDE0805 (SELV)
Standard - power supply devices for low voltage with DC output EN 61204-3
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
EMC requirements, power plant IEC61850-3
EN61000-6-5
Shipbuilding approval DNV GL, PRS, BV, LR, ABS
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
5Hz ... 100Hz resonance search 2.3g, 90min., resonance frequency
2.3g, 90min. (according to DNV GL Class C)
Approval - requirement of the semiconductor industry with regard to
mains voltage dips
SEMI F47-0706; EN 61000-4-11
Rail applications EN50121-3-2
Overvoltage category (EN 60950-1) II (≤ 5000m)
Overvoltage category (EN 61010-1) II(≤5000m)
Overvoltage category (EN 62477-1) III(≤2000m)
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings