Datasheet

FL MC EF 1300 SM SC
104980_de_02 PHOENIX CONTACT 6
4.1 UL-Hinweise
INDUSTRIAL CONTROL EQUIPMENT 11AE
Wire Range: 24-14 AWG
Torque: 5-7 (Lbs-Ins)
Environmental designation: "Open Type Device"
"Pollution Degree 2 Installation Environment"
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
A This equipment is suitable for use in ClassI, Zone2, AExnAIICT4; ExnAIICT4GcX or ClassI, Division2, Groups
A, B, C, D or non-hazardous locations only.
B Provision shall be made to prevent transient disturbances of more than 140% of the rated supply voltage.
C The device must be installed in a Class I, Zone 2 certified overall enclosure rated IP54 with tool-accessible only cover
or door and in pollution degree2 environment only.
D Unit shall be supplied by Limited Energy circuit according to clause 9.4 of UL61010-1 3rd edition of Limited Power
Source according to clause 2.5 of UL60950-1 or NEC Class2.
E Conductor temperature rating must be 72°C or higher.
F Maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.