Datasheet

https://www.phoenixcontact.com/us/produkte/2901536
Nov 13, 20132/7
I/O extension module-RAD-DOR4-IFS-2901536
Technical data
Ambient conditions
Altitude
2000 m
Vibration (operation)
In accordance with IEC 60068-2-6: 5 g, 10 Hz - 150 Hz
Shock
16 g, 11 ms
General
Surge voltage category
II
Mounting position
Any
Assembly instructions
on standard DIN rail NS 35 in accordance with EN 60715
Pollution degree
2
Housing material
PA 6.6-FR
Inflammability class according to UL 94
V0
MTTF
1087 Years (Telcordia standard, 25°C temperature, 21% operating
cycle (5 days a week, 8 hours a day))
MTTF
523 Years (Telcordia standard, 40°C temperature, 34.25%
operating cycle (5 days a week, 12 hours a day))
MTTF
204 Years (Telcordia standard, temperature 40°C, operating cycle
100% (7 days a week, 24 hours a day))
Supply
Supply voltage range
19.2 V DC ... 30.5 V DC (T-connector)
Max. current consumption
max. 55 mA (At 24 V DC, at 25°C)
Transient surge protection
Yes
Digital outputs
Number of outputs
4
Contact type
PDT
Contact material
AgSnO
2
Maximum switching voltage
250 V AC
Maximum switching voltage
24 V DC
Min. switching current
≥ 10 mA
Max. switching current
5 A (per channel)
Mechanical service life
1 x 10
7
cycles
Electrical service life
1 x 10
5
cycles (At 5 A, 250 VAC, ohmic)
Electrical service life
2 x 10
5
cycles (At 2 A, 250 VAC, cosφ 0.4)
Electrical service life
2 x 10
5
cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency
2 Hz
Switching capacity
140 W (24 V DC)
Switching capacity
120 W (30 V DC)
Switching capacity
20 W (48 VDC)
Switching capacity
18 W (60 V DC)
Switching capacity
22 W (110 V DC)
Switching capacity
40 W (220 VDC)
Switching capacity
42 W (250 VDC)