Datasheet

EEM-MA200 Order No.: 2901362
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2901362
PHOENIX CONTACT Ltd Page 2 / 4
http://www.phoenixcontact.co.uk 18-Jan-2012
Input current range Via external transformers
Input current 9999 A (primary)
5 A (secondary)
Overload capacity 6 A (Permanent)
Response threshold from measuring range
nominal value
5 mA
Precision 0.2 %
Messbereich_Leistung 0 kW ... 9999 kW
0 kvar ... 9999 kvar
0 kVA ... 9999 kVA
Precision 0.5 %
Active energy (IEC 62053-22) Class 0.5S
Reactive power (IEC 62053-23) Class 2
Description of the input Digital input
Number 1
Voltage input signal 230 V AC ± 10% (Tariff switchover: e.g., day/nighttime tariff)
Output data
Output description Transistor output, active
Number 1
Maximum switching voltage 30 V DC
Current carrying capacity 27 mA
General data
Width 72 mm
Height 90 mm
Depth 64 mm
Display LCD display, backlighting
Measuring rate approximately
Supply voltage range 200 V AC ... 277 V AC
Nominal power consumption 5 VA
Degree of protection IP52 (front), IP30 (back)
Mains type 3-phase (3 or 4-wire), 2-phase (2-wire), and single-phase (1-wire)
Color black
Conformance CE-compliant
Rated insulation voltage 300 V AC (EN 61010-1)
Surge voltage category III