User manual

STEP-UPS/24DC/24DC/3
PHOENIX CONTACT 24
11.3 Remote control (contact R1, R2)
Battery operation of the UPS can be switched on and off via
a signal to contacts R1/R2. Shutdown can take place during
mains operation or active battery operation.
Remote shutdown is deactivated
UPS in function (delivery state)
The "R1" and "R2" terminal points are short circuited
(delivery with plug-in bridge) OR 24 V DC is present at
terminal point "R2".
In the event of a voltage supply failure, the UPS switch-
es over to battery mode.
Figure 21 Remote shutdown is deactivated
11.4 Remote shutdown is activated
Terminal points “R1” and “R2” are not short circuited
and 0V is applied at terminal point “R2”.
In the event of a voltage supply failure, the UPS does
not switch over to battery mode. The device switches
off.
Figure 22 Remote shutdown active
Example 1
The remote shutdown can be used to suppress the buffering
of selective machine shutdowns. In doing so, the auxiliary
contact of the main switch is connected to R1 and R2 con-
nection terminal blocks.
Example 2
End the buffering at a specific time (e.g., following shutdown
of another machine part). Remote shutdown can be acti-
vated with a relay (N/C contact).
NOTE:
In the event of a supply voltage failure, the
UPS switches over to battery operation. The
load connected to the DC output is supplied
by the battery module.
R2
R1
OFF
ON
+24 V DC
R2
R1
OFF
ON
R2
R1
OFF
ON