Datasheet

https://www.phoenixcontact.com/us/produkte/2868033
Nov 14, 20132/14
Type 2 surge protection device-VAL-MS 60/FM-2868033
Technical data
General
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
1
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
1L-N/PE
Protective circuit
IEC test classification
II
IEC test classification
T2
EN type
T2
Nominal voltage U
N
60 V AC/DC
Nominal voltage U
N
- 48 V DC (RRH)
Nominal voltage U
N
30 V DC (L/R: 20-60 ms)
Nominal voltage U
N
60 V DC (L/R: 10-20 ms)
Maximum continuous operating voltage U
C
75 V AC
Maximum continuous operating voltage U
C
100 V DC
Maximum continuous operating voltage U
C
(L-N)
75 V AC
Maximum continuous operating voltage U
C
(L-PEN)
75 V AC
U
T
(TOV-proof)
100 V AC (5 s)
Nominal frequency f
N
50 Hz
Nominal frequency f
N
60 Hz
Residual current I
PE
≤ 0.45 mA
Standby power consumption P
C
≤ 35 mVA
Max. discharge current I
max
(8/20) µs
40 kA
Max. discharge current I
max
(8/20) µs maximum (L-N)
40 kA
Max. discharge current I
max
(8/20) µs maximum (L-PEN)
40 kA
Nominal discharge current I
n
(8/20) µs
15 kA
Nominal discharge current I
n
(8/20) µs (L-N)
15 kA
Nominal discharge current I
n
(8/20) µs (L-PEN)
15 kA
Impulse discharge current (10/350) µs, charge
2 As
Impulse discharge current (10/350) µs, peak value l
imp
4 kA
Max. energy absorption (2 ms)
190 J
Voltage protection level U
p
≤ 500 V
Voltage protection level U
P
(L-N)
≤ 500 V
Voltage protection level U
P
(L-PEN)
≤ 500 V
Residual voltage
≤ 500 V
Residual voltage
≤ 325 V (at 5 kA)
Residual voltage
≤ 275 V (at 3 kA)
Residual voltage (L-N)
≤ 325 V (at 5 kA)
Residual voltage (L-PEN)
≤ 325 V (at 5 kA)
Response time
≤ 25 ns