Datasheet

https://www.phoenixcontact.com/us/produkte/2866776
Nov 14, 20132/10
Power supply unit-QUINT-PS/ 1AC/24DC/20-2866776
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
Short-term input voltage
300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
5.1 A (120 V AC)
Current consumption
2.3 A (230 V AC)
Inrush surge current
< 20 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 20 ms (230 V AC)
Input fuse
12 A (slow-blow, internal)
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
20 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
26 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24
V DC)
Output current
120 A (SFB technology, 12 ms)
Output current
26 A (U
In
≥ 100 V AC)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
B10
Magnetic fuse tripping
B16
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Magnetic fuse tripping
C6
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 30 mV
PP
(with nominal values)
Maximum power dissipation NO-Load
8 W