Datasheet

https://www.phoenixcontact.com/us/produkte/2864587
Nov 13, 20132/6
Temperature measuring transducer-MCR-FL-TS-LP-I-
EX-2864587
Technical data
Input data
Connection method
2, 3, 4-wire
Input signal range
10 Ω ... 400 Ω (min. measurement range 10 Ω)
Input signal range
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
Input signal range
-10 mV ... 100 mV (min. measurement range 5 mV)
Output data
Signal output
Current output
Current output signal
4 mA ... 20 mA
Current output signal
20 mA ... 4 mA
Max. current output signal
≤ 23 mA
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange
3.8 mA ... 20.5 mA
Load/output load current output
≤ 520 Ω (At U
V
= 24 V; U
supply
- 12 V / 0.023 A)
Power supply
Name
Loop-powered
Supply voltage range
12 V DC ... 30 V DC
Max. current consumption
< 3.5 mA
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
Connection method
Pluggable screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
Step response (10-90%)
< 2 s
Pickup delay
4 s
Configuration
With HART protocol
Inflammability class according to UL 94
V0
Standards/regulations
NAMUR recommendation NE 21
Housing material
Polyamide PA non-reinforced
Color
green
Line monitoring
NE 43