Datasheet
MINI MCR-SL-PT100-UI-200
102478_en_02 PHOENIX CONTACT 3
3.1 Order key
(standard configuration entered as example)
Description Type Order No. Pcs. / Pkt.
MCR temperature transducer, can be configured, for Pt!100 temperature
sensors, with screw connection, order configuration
MINI MCR-SL-PT100-UI-200 2864309 1
MCR temperature transducer, can be configured, for Pt!100 temperature
sensors, with spring-cage connection, order configuration
MINI MCR-SL-PT100-UI-200-SP 2864192 1
MCR temperature transducer, configurable, for Pt!100 temperature sen-
sors, with screw-connection, not configured
MINI MCR-SL-PT100-UI-200-NC 2864370 1
MCR temperature transducer, configurable, for Pt!100 temperature sen-
sors, with spring-cage connection, not configured
MINI MCR-SL-PT100-UI-200-SP-NC 2864202 1
3Ordering data
Accessories Type Order No. Pcs. / Pkt.
DIN rail connector (T-BUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN!60715
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 2869728 10
MCR power terminal block for supplying several MINI Analog modules via
the DIN rail connectors, with screw connection, current consumption up to
max. 2!A
MINI MCR-SL-PTB 2864134 1
MCR power terminal block for supplying several MINI-ANALOG modules
via the DIN rail connectors, with spring-cage connection, current consump-
tion up to max. 2!A
MINI MCR-SL-PTB-SP 2864147 1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A, ATEX approval
MINI-PS-100-240AC/24DC/1.5/EX 2866653 1
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI MCR-SL-V8-FLK 16-A 2811268 1
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
MINI MCR DKL 2308111 10
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
MINI MCR-DKL-LABEL 2810272 10
1)
Failure information:
Measuring range overrange Cable break
0 ... 20 mA 4 ... 20 mA 0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10 V
A 20.5 mA 20.5 mA 10.25 V 21 mA 21 mA 10.5 V
B 20.5 mA 20.5 mA 10.25 V 21 mA 21 mA 10.5 V
C 20 mA 20 mA 10 V 21 mA 21 mA 10.5 V
D 20 mA 20 mA 10 V 0 mA 4 mA 0 V
Measuring range underrange Short circuit
0 ... 20 mA 4 ... 20 mA 0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10 V
A 0 mA 4 mA 0 V 0 mA 4 mA 0 V
B 0 mA 3.5 mA 0 V 0 mA 3 mA 0 V
C 0 mA 4 mA 0 V 21 mA 21 mA 10.5 V
D 0 mA 4 mA 0 V 0 mA 4 mA 0 V
Order No. Connection
method
Measuring range [°C] Output Failure
information
1)
Factory calibration certificate
Start Finish
2864309 / 3 / 0 / 100 / OUT01 / A / NONE
2 ! 2-wire 0 Range
(increment)
OUT01 ! 0 ... 20 mA A NONE ! Without factory calibration
2864309 ! 3 ! 3-wire -5 OUT02 ! 4 ... 20 mA B YES ! With factory calibration cer-
tificate (a fee is charged)
...-PT100-UI-200 4 ! 4-wire -10 OUT03 ! 0 ... 10 V C
-15 0 ... 200 (5 K) OUT05 ! 0 ... 5 V D
2864736 ! -20 OUT06 ! 1 ... 5 V YESPLUS ! Factory calibration certifi-
cate with 5 measuring
points (a fee is charged)
...-PT100-UI-200-SP -30 OUT07 ! 20 ... 0 mA
-40 OUT08 ! 20 ... 4 mA
-50 OUT09 ! 10 ... 0 V