Datasheet

https://www.phoenixcontact.com/us/produkte/2862945
Nov 14, 20132/7
Inline terminal-IB IL 24 DO 8-PAC/SN-2862945
Technical data
Ambient conditions
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
130 g
Note on weight specifications
Without plug
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Diagnostics messages
Short-circuit / overload of the digital outputs Error message in the
diagnostic code (bus) and display (2 Hz) via the LED (D) on the
module
Interfaces
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC
Communications power U
L
7.5 V (via voltage jumper)
Current consumption
max. 60 mA (from the local bus)
Inline potentials
Communications power U
L
7.5 V DC
Current consumption from U
L
max. 60 mA
Segment supply voltage U
S
24 V DC (nominal value)
Current consumption from U
S
max. 4 A
Digital outputs
Output name
Digital outputs
Connection method
Spring-cage connection
Connection method
2, 3, 4-wire
Number of outputs
8
Protective circuit
Overload protection, short-circuit protection of outputs
Output voltage
(U
S
- 1 V)