Datasheet

https://www.phoenixcontact.com/us/produkte/2859482
Nov 13, 20132/7
Type 2 surge protection device-VAL-CP-2C-175-2859482
Technical data
General
Standards for air and creepage distances
IEC 60664-1
Standards for air and creepage distances
IEC 61643-1
Surge voltage category
III
Pollution degree
2
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
2
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
2L-N/PE
Protective circuit
IEC test classification
II
IEC test classification
T2
EN type
T2
Nominal voltage U
N
120 V AC (2P/PEN)
Nominal voltage U
N
208 V AC (Phase - Phase)
Maximum continuous operating voltage U
C
175 V AC
Maximum continuous operating voltage U
C
(L-PEN)
175 V AC
U
T
(TOV-proof)
240 V AC (5 s)
Nominal frequency f
N
50 Hz
Nominal frequency f
N
60 Hz
Rated load current I
L
40 A (40 A ... 63 A)
Rated load current I
L
63 A (10 mm²)
Residual current I
PE
≤ 300 µA
Standby power consumption P
C
≤ 17.5 mW
Max. discharge current I
max
(8/20) µs maximum (L-PEN)
80 kA (all channels)
Nominal discharge current I
n
(8/20) µs (L-PEN)
40 kA (all channels)
Nominal discharge current I
n
(8/20) µs (L-PEN)
20 kA (1 channel)
Voltage protection level U
P
(L-PEN)
≤ 850 V (at I
n
)
Residual voltage (L-PEN)
≤ 700 V (at 10 kA)
Residual voltage (L-PEN)
≤ 600 V (at 5 kA)
Residual voltage (L-PEN)
≤ 550 V (at 3 kA)
Residual voltage (L-PEN)
≤ 850 V
Response time (L-PEN)
≤ 25 ns
Max. required backup fuse with branch wiring
125 A (gL/gG)
Max. required backup fuse with V-type through wiring
40 A (gL/gG)
Short-circuit resistance I
P
with max. backup fuse (effective)
25 kA
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block