7 Termination resistor
7.1 Activating termination resistor and disabling
outgoing bus cables
Figure 23 Termination resistor
The termination resistors are activated at the start and finish
of the bus system using the slide switch (pos. 2 in Figure 3,
pos. 3 in Figure 10 and pos. 4 in Figure 20). The connection
terminal blocks (2A/2B) for the outgoing bus cable are
disabled at the same time.
The termination resistor must be deactivated at all the bus
system's other node points.
7.2 Linear extension according to PROFIBUS
specification
Transmission speed
in kbps
Associated segment
length
9.6 / 19.2 / 45.45 / 93.75 1200 m
187.5 1000 m
500 400 m
1500 200 m
3000 / 6000 / 12000 100 m
≈
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON ON
OFFOFFOFFOFF
Start
Finish