Datasheet

https://www.phoenixcontact.com/us/produkte/2320908
Nov 9, 20132/10
Power supply unit, dip coated-QUINT-PS/ 1AC/24DC/ 5/
CO-2320908
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C (ATEX/IECEx: -25°C ... +60°C)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
100 % (at 25 °C, no condensation)
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 410 V DC + 5% (UL 508: ≤ 250 V DC)
Short-term input voltage
300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
1.2 A (120 V AC)
Current consumption
0.6 A (230 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 25 ms (120 V AC)
Power failure bypass
> 25 ms (230 V AC)
Input fuse
5 A (slow-blow, internal)
Choice of suitable fuses
6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
5 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
7.5 A (U
In
≥ 100 V AC)
Output current
30 A (SFB technology, 12 ms)
Output current
7.5 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
=
24 V DC)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
C2
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 40 mV
PP
(with nominal values)