Datasheet

https://www.phoenixcontact.com/gb/products/1648115
06/21/2018Page2/7
Contact insert-HC-B 6-I-UT-M-1648115
Technical data
General
Contact numbering 1 - 6
Conductor cross section 0.5 mm² ... 2.5 mm² (applies to stranded conductors with ferrules)
Connection cross section AWG 20 ... 14
Stripping length of the individual wire 8 mm
Assembly instructions
Coding also using the CP-HC (1686478) coding profiles. HC-B6../ HC-
B10..for two coding profiles. HC-B16../ HC-B24..for four coding profiles.
Connection Connectors may only be actuated when there is no load/voltage.
Ambient conditions
Ambient temperature (operation) -40 °C ... 125 °C (including heating up of contacts)
Material data
Contact material Copper alloy
Contact surface material Ag
Contact carrier material PC
Electrical characteristics
Rated voltage (III/3) 500 V
Rated surge voltage 6 kV
Rated current 24 A
Standards and Regulations
Connection in acc. with standard CSA
Constructional and testing regulations DIN EN 61984
DIN EN 60664
IEC 60352
Flammability rating according to UL 94 V0
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Schematic diagram
6
5
4
3
2
1
Connector pin assignment, connection side
Dimensional drawing
32,4
44
50
27
34
Male insert