Install Instructions

© COPYRIGHT 2020 PECO, INC. ALL RIGHTS RESERVED. P/N 73676 3220-2372 REV 04
1
THE PECO COMMERCIAL T8168 THERMOSTAT
Thank you for choosing a PECO
®
Performance PRO thermostat. The T8168
thermostat is intended for commercial and residential enviroments. It supports
both programmable and non-programmable operation.
Key features include: auto-changeover; optional remote sensor; three levels of
keypad lockout with optional PIN access code; a heat/cool Demand Indicator;
up to four scheduled events per day, a 365-day calendar, 20 holidays, holiday
override and temporary override.
Applications
The PECO
®
Performance PRO™ T8168 applications include fan coil, PTAC and
conventional system with a single, multi speed or 0-10 VDC Fan.
System Mode Selections: Off-Heat-Cool-Auto
ON-OFF Heat/Cool Outputs: Up to 2 Heat, 2 Cool
Proportional Heat/Cool Outputs: Three Wire Floating or 0-10 VDC Control
Fan Control: Cycling (Auto) or Continuous (On); Up to 3 Speeds or Staged
Permanent Memory: All device settings are stored in permanent memory.
Optional Connections: Remote Sensor, Pipe Sensor, Fault Detection and Setback
RATINGS
Outputs: Y1, Y2, W1, W2, G, G1
24 VAC (20-30 VAC); 50/60 Hz
10 VA
Outputs: WD, GD, YD
0-10 VDC: Loads must be 1.2K ohms minimum
4-20 mA: Loads must be 600 ohms maximum
This thermostat uses triacs switching for accuracy and quiet operation.
INSTALLATION INSTRUCTIONS
Select an appropriate thermostat location
Locate the thermostat about four feet (1.2m) above the oor on a wall with good
ventilation, average temperature and good response to temperature changes.
The T8168 may be mounted on a:
• Horizontal or vertical 2” X 4” device box
• Horizontal 4” X 4” device box
• Flat surface
Do not locate the thermostat where it can be affected by:
• Direct sunlight
• Drafts or dead areas behind doors
• Radiating heat or cool from appliances or equipment
• Concealed pipes or chimneys
• Outside walls or unheated/uncooled areas
Required components (not included, unless otherwise specied):
• Screws and wall anchors (included)
Screwdrivers: Phillips (for wallplate); small athead (for terminal blocks)
• Drill with 3/16” drill bit (or 7/32” for plaster)
• Wire cutter and stripper
• Level
TERMINAL BLOCK DESIGNATIONS
Terminal \Description Return To
24 VAC-1 24 VAC 1 (UNSWITCHED)
24 VAC-2 24 VAC 2
24 VAC-2 24 VAC 2
Y1 COOL 1 COOL Open (TWF) 24 VAC 1
W1 HEAT 1 HEAT Open (TWF) 24 VAC 1
Y2 COOL 2 or FAN 3 (MED) COOL Close (TWF) 24 VAC 1
W2 HEAT 2 HEAT Close (TWF) 24 VAC 1
G FAN 1 (HI) 24 VAC 1
G1 FAN LO or DAMPER Configurable 24 VAC 1
YD 0-10VDC COOL (4-20mA) 24 VAC 2
WD 0-10VDC HEAT (4-20mA) 24 VAC 2
GD 0-10VDC FAN (4-20mA) 24 VAC 2
S1 REMOTE SENSOR, FAULT DETECTION SC
S2 PIPE SENSOR SC
SC DC/SENSOR COMMON
4A Not Available
4B Not Available
4C Not Available
• WARNING: Disconnect power before beginning installation.
• CAUTION: Use copper wire only
• CAUTION: Do not connect unused wires together
TECHNICAL SPECIFICATIONS
Temperature Control Range: 50° to 90° F (10° to 32° C)
Differential: 1° F (0.5°C)
Input Power: 24 VAC (20-30 VAC) 50/60 Hz (+/- 10%)
Terminal Connections: 14-24 AWG stranded or solid wire
Operating Temperature: 0° to 120°F (-18° to 49°C)
Shipping/Storage Temperature: -20° to 130°F (-29° to 54°C)
Operating Humidity: 5% to 95% RH, non-condensing
Physical Dimensions: 4.3” H x 5.7” W x 1.3”D
Proportional Output Band Width: 2°F (1°C)
Proportional Stroke Time Default: 2 Minutes (Congurable)
T8168 INSTALLATION GUIDE
CONTROL
SYSTEMS
CAUTION!
24 VAC low-voltage thermostat. Do not install on voltages higher than 30 VAC.
Use copper wire only
Use care to avoid electrostatic discharge to the thermostat.
!
Note: A load must be
connected to outputs
for testing
Mounting holesMounting holes
Wiring passage
WARNING
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
• Failure to observe safety information and comply with instructions could
result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
• To avoid electrical shock or damage to equipment, disconnect power
before installing or servicing and use only wiring with insulation rated for full
thermostat operating voltage.
• Use care to avoid electrostatic discharge.
To avoid potential re and/or explosion do not use in potentially ammable
or explosive atmospheres.
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered system whose
specications and performance characteristics are not designed or
controlled by PECO
®
. Review applications and national and local codes to
assure that the installation will be functional and safe.
!
!