Install Instructions

AirCycler® g2
INSTALLATION & USER’S MANUAL
INTRODUCTION
In the past, homes depended on natural leaks for ventilation.
Today, energy efficient homes are built to reduce natural
ventilation and leaks. Inadequate ventilation can increase
indoor air pollutants to harmful levels. Indoor air quality
is typically 5 to 10 times more polluted than outside air.
Controlled ventilation provides adequate air flow to the
home without compromising its efficiency.
SAFETY CONSIDERATIONS
Read and follow manufacturer’s instructions carefully.
Follow all local electrical codes during installation. All
wiring must conform to local and national electrical codes.
Improper wiring or installation may result in personal injury
or product and property damage.
INSTALLATION CONSIDERATIONS
The AirCycler® g2 requires 24VAC (R and C terminals) to
be connected for proper operation. The controller will not
operate without these two connections.
The wires (R, C, & W ) from the air handler to the thermostat
can run parallel with the wiring from the AirCycler® g2 to
the air handler. The fan wire (G) must be interrupted by the
AirCycler® g2. Some thermostats do not require a common
(C) connection. The AirCycler® g2 requires this for power,
which must be wired to the furnace.
DAMPER LOCATION
The fresh air damper can be located anywhere in the inlet
duct. Minimize the length of the inlet duct to improve air
flow and improve system efficiency. It is recommended
that the damper be as close to the return air plenum and
the AirCycler® g2 controller as possible, and the inlet duct
connect to the return plenum upstream of the system filter,
and down- stream of any duct mounted sensors.
DAMPER INSTALLATION
The damper may be installed in any position. It is
recommended to install it with the motor at the 12 o’clock
position if mounted horizontally. Air may flow through in
either direction, although it is recommended to install with
the crimped end as the outlet. Use care to avoid distorting
the damper housing and provide adequate support. Upon
system start up be sure to set damper power switch to
UP or AUTOMATIC position.
CHOOSE A FRESH AIR LOCATION
ASHRAE recommends that the fresh air intake be located
at least 10 ft. from any source of pollutants, such as auto
exhaust, dryer exhaust, exhaust from any fuel-burning
appliances, etc. Avoid installation near odor sources such as
garbage bins or barbecue grills. A minimum of 3 ft. above
ground is recommended to avoiding ingress of leaf litter,
grass clippings, etc. Do not use a crawl space, basement, or
attic as a source of intake air. Always be sure to comply with
local building codes and requirements regarding fresh air
inlets.
BATTERY (MODEL CR1220)
The AirCycler® g2 is equipped with a real time battery
backed-up clock for use with the Operation Hours
setting ONLY. If not setting the hours of operation, the
included battery is not required. All other settings are
saved in nonvolatile memory.
NORMAL OPERATION DISPLAY
• When the AirCycler® g2 is in Normal Operation,
the display will show the percentage of ventilation
complete for the current hour.
• If the central fan is on, the FAN and ON icon will be
illuminated.
• If the exhaust (bath) fan is on, the EXH icon will be
illuminated.
• If the outside fresh air damper is open, the OA icon will
be illuminated.
• If the exhaust fan is running its delay time after
bathroom occupancy, the delay time countdown, MIN
and EXH icons will be illuminated.
• If the thermostat is calling for heat or cool, the FAN
icon will be illuminated without the ON icon.
• The ON icon is only illuminated when the AirCycler® g2
has forced the central fan on. (Calculated Time Mode
Only)
• Press the MODE key at any time during normal
operation to set the current time of the day.
• If the EXH icon is blinking, it indicates the exhaust fan
has been on for more than 4 hours or the connection
to the AirCycler® g2 controller was lost.
APPENDIX B - Troubleshooting
Blank Display on the AirCycler® g2 controller.
Solution Check:
1. Confirm that the furnace has power.
2. Confirm that the thermostat is operational.
3. Confirm that the furnace will call for heat from the
thermostat.
4. Confirm that the fan operates with a fan only signal
from the thermostat
5. Confirm that the furnace is providing 24VAC to the
AirCycler® g2
6. Confirm the wiring conforms to the wiring diagram.
7. Make sure the cover is firmly seated on the base.
The AirCycler® g2 turns the furnace fan on and o, but
the motorized damper does not cycle.
Solution Check:
1. Confirm that the AirCycler® g2 is providing a 24VAC
signal to the motorized damper.
2. Confirm the 24 VAC motorized damper is operational
by powering directly with a 24 VAC signal
3. Verify there is continuity in the wiring between the
damper and the AirCycler® g2
4. Confirm damper power switch is in up or automatic
position
The A/C turns on during fan cycling calls
Solution Check:
1. Verify that the wiring conforms to the wiring diagram.
2. Confirm that the G wire is properly connected.
Note: The G wire must be interrupted by the AirCycler®
g2. Do not run the G wire in parallel.
The EXH icon is ashing.
This indicates the g2 controller has seen the
FanConnect
exhaust fan on for more than 4 hours.
Solution Check:
1. Turn o exhaust fan.
2. Check wiring from FanConnect switch to g2
controller.
For more troubleshooting and frequently asked questions,
visit: www.aircycler.com/pages/troubleshooting
For Limited Warranty information please visit:
www.aircycler.com/products
Vnc - Normal Closed Vent
R - 24VAC Power
W - Heating
Gt - Fan From Thermostat
Gf - Fan to Furnace
C - Common
V - Vent
Ex - Exhaust Fan
Technical Support:
1.877.FAN.CONTrol
(1.877.326.2668)
Vnc Ex
THE EXHAUST
FAN IS ON
THE THERMOSTAT
HAS TURNED ON
THE CENTRAL FAN
THE AIRCYCLER® G2
HAS FORCED THE FAN
THE DAMPER
IS OPEN
PERCENTAGE OF
VENTILATION COMPLETE
Ventilation Products
VENTILATION MADE BREEZY!™
A BREEZE TO INSTALL • A BREEZE TO USE!
AIRCYCLER®
411 PLAIN STREET
MARSHFIELD, MA 02050
WWW.AIRCYCLER.COM
This product may be protected by one or more of the
following patents and patents pending: 8185244,
7258280, 6431268, 881806, 547017, Canada 2245135

Summary of content (2 pages)