TECHNICAL DATA & SERVICE MANUAL Outdoor Unit Indoor Unit Shows S-26PU1U6 Shows U-26PE1U6 Model No.
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back.
When Servicing CAUTION • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. WARNING NOTICE • Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.
Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” Tubing size: Be sure to use the sizes indicated in the table below. Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
Configuration and characteristics of cylinders 3-2. Use R410A exclusive cylinder only. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if the amount in the charging cylinder is less than 20%.
Contents Section 1: SPECIFICATIONS ..................................................................................................... 1-1 1-1 Unit SpecifIcations .............................................................................................. 1-2 1-2 Major Component SpecifIcations ...................................................................... 1-20 1-3 Other Component SpecifIcations ...................................................................... 1-35 1-4 Dimensional Data......
1. SPECIFICATIONS 1-1. Unit Specifications.................................................................................................... 1-2 1-2. Major Component Specifications .......................................................................... 1-20 1-3. Other Component Specifications .......................................................................... 1-35 1-4. Dimensional Data ....................................................................................................
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. 1 Indoor Unit S-26PU1U6 Outdoor Unit U-26PE1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] 29,800 [8,000~29,800] (17˚F)** BTU / h 18,300 Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.1 9.
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. Indoor Unit S-36PU1U6 Outdoor Unit U-36PE1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600] 37,600 [8,000~37,600] (17˚F)** BTU / h 20,000 Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 8.
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. 1 Indoor Unit S-42PU1U6 Outdoor Unit U-42PE1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500] 48,000 [8,000~48,000] (17˚F)** BTU / h 31,800 Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 9.
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. Indoor Unit S-26PU1U6 Outdoor Unit U-26PS1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] (17˚F)** BTU / h Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. 1 Indoor Unit S-36PU1U6 Outdoor Unit U-36PS1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600] (17˚F)** BTU / h Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications 4-Way Cassette Type MODEL No. Indoor Unit S-42PU1U6 Outdoor Unit U-42PS1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500] (17˚F)** BTU / h Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications Wall Mounted Type MODEL No. 1 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. 1 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. 1 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. 1 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Low Silhouette Duct Type MODEL No. 1 Indoor Unit S-26PF1U6 Outdoor Unit U-26PE1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000] 28,600 [8,000~28,600] (17˚F)** BTU / h 17,100 Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in.WG External Static Pressure 0.2:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications Low Silhouette Duct Type MODEL No. Indoor Unit S-36PF1U6 Outdoor Unit U-36PE1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] 36,200 [8,000~36,200] (17˚F)** BTU / h 20,200 Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 1060 / 920 / 750 in. WG External Static Pressure 0.24:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 13.
1. Specifications 1-1 Unit Specifications Low Silhouette Duct Type MODEL No. 1 Indoor Unit S-26PF1U6 Outdoor Unit U-26PS1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000] — (17˚F)** BTU / h Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in. WG External Static Pressure 0.2:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications Low Silhouette Duct Type MODEL No. Indoor Unit S-36PF1U6 Outdoor Unit U-36PS1U6 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] — (17˚F)** BTU / h Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 1060 / 920/ 750 in. WG External Static Pressure 0.24:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 13.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-26PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller (Supplied / Optional) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CR-26PU1U6-P Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 41D6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-36PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CR-26PU1U6-P Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 81A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-42PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller (Supplied / Optional) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CR-26PU1U6-P Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 81A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-26PK1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Optional / Supplied ) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CB-KR254GXH56A Control circuit fuse 250 V, 5 A Fan Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4-1/3 (110), L39 (990) Fan motor Model KFT4Q - 31A6P - C Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-26PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-1/8(130)) Fan motor Model SR4X - 51A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-36PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 101C6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-42PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 101C6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-26PF1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 71B6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. S-36PF1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFC4X-141A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit U-26PE1U6 MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0U Nominal output W 1,500 Compressor oil cc 650 Coil resistance Ω C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. U-36PE1U6 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0U Nominal output W 1,500 Compressor oil cc 650 Coil resistance Ω C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. P-42PE1U6 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-9RVN273H0W Nominal output W 2,700 Compressor oil cc 1,900 Coil resistance Ω C – R : 0.169 (Ambient temperature 25 °C) R – S :0.169 C – S :0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. U-26PS1U6 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0U Nominal output W 1,500 Compressor oil cc 650 Coil resistance Ω C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. U-36PS1U6 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0U Nominal output W 1,500 Compressor oil cc 650 Coil resistance Ω C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. U-42PS1U6 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-9RVN273H0W Nominal output W 2,700 Compressor oil cc 1,900 Coil resistance Ω C – R : 0.169 (Ambient temperature 25 °C) R – S :0.169 C – S :0.
1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL No. U-26PE1U6, U-26PS1U6 Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL No. U-36PE1U6, U-36PS1U6 Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL No. U-42PE1U6, U-42PS1U6 Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 26 Type 10-9/32 8-11/16 4-7/8 Min. 2-15/32 3 11-1/2 9-1/8 X-view 13-11/32 3-15/16 Min.
1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 36, 42Type 11-15/32 9-19/32 13-11/32 3-15/16 4-7/8 Min. 2-15/32 X-view Min.
1. Specifications 1-4 Dimensional data Indoor unit : Wall Mounted Type Drain and wiring port (3-5/32) Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (5/8") Flare connection Drain hose OD 45/64 1 Dimension : inch 1-40 SM830203-01_PAC-i_US-letter.
1.
1.
1.
1.
1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct Type 13/32 Thickness more than T1/16 inch 8-9/32 31/32 2-ø1/8 (Hole) Flange for the air intake duct (Field supply) : For Concealed Duct Type 31/32 12-1/32 31/32 10-1/4 (O.D.) 29/32 23/32 1 A 11/32 F G E H B (O.D.
1. Specifications 1-4 Dimensional Data (B) Outdoor Unit: U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 1 1-46 SM830203-01_PAC-i_US-letter.
1. Specifications 1-4 Dimensional Data (B) Outdoor Unit: U-42PE1U6, U-42PS1U6 1 1-47 SM830203-01_PAC-i_US-letter.
1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Unit : U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 Indoor Unit : 26, 30, 36 Types 1 1-48 SM830203-00_PAC-i_US-letter.indb48 48 SM830203-01_PAC-i_US-letter.
1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Unit: U-42PE1U6, U-42PS1U6 Indoor Unit: 42 Type 1 1-6 Operating Range Cooling Heating Temperature Indoor Air Intake Outdoor Air Intake Maximum 90 °F DB / 77 °F WB 115 °F DB Minimum 64 °F DB / 57 °F WB 14 °F DB Maximum 86 °F DB 64 °F WB / 75 °F DB Minimum 61 °F DB -4 °F WB / -4 °F DB 1-49 SM830203-01_PAC-i_US-letter.indb49 49 SM830203-00_PAC-i_US-letter.
1. Specifications 1-7 Capacity Correction Graph According to Temperature Condition U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 U-42PE1U6, U-42PS1U6 1 1-50 SM830203-01_PAC-i_US-letter.
1. Specifications 1-8 Noise Criterion Curves 4-Way Cassette Type MODEL : S-26PU1U6 SOUND LEVEL : HIGH 38 dB(A), NC 31 LOW 31 dB(A), NC 23 CONDITION : Center, Under the unit 4.9 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.
1. Specifications 1-8 Noise Criterion Curves Wall Mounted Type S-26PK1U6 CONDITION : Distance 3.3 ft., Under the unit 3.3 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz 1 1-52 SM830203-01_PAC-i_US-letter.
1. Specifications 1-8 Noise Criterion Curves Ceiling Type MODEL : S-26PT1U6 MODEL SOUND LEVEL : HIGH 40 dB(A), NC 34 LOW : S-36PT1U6 SOUND LEVEL : HIGH 46 dB(A), NC 39 36 dB(A), NC 26 LOW 37 dB(A), NC 31 CONDITION : Distance 3.3 ft., Under the unit 3.3 ft. CONDITION : Distance 3.3 ft., Under the unit 3.3 ft.
1. Specifications 1-8 Noise Criterion Curves Low Silhouette Duct Type MODEL : S-36PF1U6 SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 CONDITION : Under the unit 4.9 ft. CONDITION : Under the unit 4.9 ft.
1. Specifications 1-8 Noise Criterion Curves Outdoor Units U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 1 U-42PE1U6, U-42PS1U6 REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an nechoic room.
1. Specifications 1-9 Increasing the Fan Speed Electrical component box If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: Jumper cable Fan motor Jumper cable Fan motor socket (At shipment) (1) Remove 4 screws on the electrical component box and remove the cover plate.
1. Specifications 1-10 Air throw distance chart 4-Way Cassette Type Model: 26 Type HORIZONTAL DISTANCE (ft.) 0 3 7 10 13 17 20 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 AXIS AIR VELOCITY 3 7 10 13 2111_X_I 1 Model: 36, 42 Type HORIZONTAL DISTANCE (ft.) 0 3 7 10 13 17 20 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.
1. Specifications 1-10 Air throw distance chart Wall Mounted Type Horizontal distance (ft.) Model: 26 Type Axis air velocity (ft./sec.) Vertical distance (ft.) 0 5 10 13 COOLING - - - - - HEATING 1 FAN SPEED HIGH HIGH ROOM AIR TEMP. 80°F 70°F FLAP ANGLE 0°, 22.5°, 45° 45°, 67.5° 1-58 SM830203-01_PAC-i_US-letter.
1. Specifications 1-10 Air throw distance chart Ceiling Type Model: 26 Type HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17 20 23 26 29 33 0 3 AXIS AIR VELOCITY 7 10 13 17 2115_T_I Model: 36 Type HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17 20 23 26 29 1 33 0 3 AXIS AIR VELOCITY 7 10 13 17 2116_T_I Model: 42 Type HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft.
1. Specifications 1-11. ELECTRICAL WIRING General Precautions on Wiring 1 (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) To prevent possible hazards from insulation failure, the unit must be grounded.
1.
1. Specifications Stranded wire Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. Strip 3/8 in. WARNING Ring pressure terminal When connecting each power wire to the corresponding terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate. Fig.
1. Specifications 1-12. Installation Instructions Outdoor Unit 1. Tubing Size Main tubing L H1 Single Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2.
1. Specifications CAUTION 1. This unit requires no additional refrigerant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant charge is required. Refer to Table 1-3. 2. In case of multi type installation, indoor units should be installed within the same room. If multi type indoor units are installed in different rooms, temperature control may develop problems because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main unit).
1. Specifications 3. SELECTING THE INSTALLATION SITE 3-1. Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 1-3) damp, humid or uneven locations Exhaust fan Hot air Heat source Outdoor unit DO: choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly. allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig.
1. Specifications 3-2. Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: Air discharge it is difficult to keep a space of min. 20" between the air discharge outlet and an obstacle. the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by. Refer to Fig. 1-7. Air discharge 3-3.
1. Specifications 3-5.
1.
1. Specifications Reference diagram for air-discharge chamber (field supply) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. Min. 39-3/8 Min. 7-7/8 (1) Single-unit installation Unit: inch CAUTION The top and both sides must remain open.
1. Specifications 3-6.
1.
1. Specifications Reference diagram for snow-proof vents – 1 Space requirements for setting – (1) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 [Obstacle to the rear of unit] [Obstacle to the front of unit] Top is open: (1) Single-unit installation Min. D Min. A Min. H Top is open: (1) Single-unit installation (2) Obstacles on both sides Min. B (2) Multiple-unit installation (2 or more units) Min. C (3) Multiple-unit installation (2 or more units) Min. I Min. G Min. I Min. J 1 Min. E Min.
1. Specifications Reference diagram for snow-proof vents – 2 Space requirements for setting – (2) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Q Dimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16 in. or more. Min. O Min.
1. Specifications 4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Installing the Outdoor Unit Use concrete or a similar material to create the base, and ensure good drainage. Ordinarily, ensure a base height of 2". or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 6". or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.
1. Specifications Indoor Unit Ceiling Type 5. SELECTING THE INSTALLATION SITE Ceiling 5-1. Indoor Unit AVOID: Wall areas where leakage of flammable gas may be expected. Min. 10 inch places where large amounts of oil mist exist. direct sunlight. Min. 10 inch Front view NOTE locations near inverter lamps which may affect the performance of the unit. The rear of the indoor unit can be installed flush against the wall.
1. Specifications 6. HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette Type (U1 Type) 6-1. Suspending the Indoor Unit Hole-in-anchor Hole-in-plug This unit uses a drain pump. Use a level gauge to check that the unit is level. Concrete Insert 6-2. Preparation for Suspending (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs.
1. Specifications (2) The length of each suspension bolt must be appropriate for a distance between the bottom of the bolt and the bottom of the ceiling of 5/8" or more as shown in Fig. 1-15. (3) Thread the 2 hexagonal nuts (field supply) and washers onto the 4 suspension bolts as shown in Fig. 1-16. Use 2 sets of nuts and washers (upper and lower), so that the unit will not fall off the suspension lugs.
1. Specifications 6-4. Installing the Drain Piping Transparent part for checking drainage (1) Prepare standard hard PVC pipe for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent part allows you to check drainage. (Fig. 1-17) CAUTION Packing (supplied) Tighten the hose clamps so their locking nuts face upward. (Fig.
1. Specifications 6-5. Checking the Drainage After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water. WARNING Do not supply power to the unit until the tubing and wiring to the outdoor unit are completed. (1) Take off the tube cover and through the opening, slowly pour about 0.3 gal of water into the drain pan to check drainage.
1. Specifications Ceiling Panel CAUTION Latch Screw Never touch or attempt to move the air direction louver by hand or you may damage the unit. Instead, use the remote controller if you want to change the direction or air flow. Air-intake grille 6-6. Before Installing the Ceiling Panel (1) Remove the air-intake grille and air filter from the ceiling panel. (Figs. 1-24 and 1-25) Ceiling panel (a) Remove the 2 screws on the latch of the airintake grille. (Fig. 1-24) 1 Fig.
1. Specifications 6-7. Installing the Ceiling Panel (1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit. NOTE The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size. Confirm that the catches are correctly matched between the ceiling panel and the indoor unit body. (2) Next, check to see that the ceiling panel is properly aligned with the seamline of the ceiling.
1. Specifications 6-9. Duct for Fresh Air For fresh air intake There is a duct connection part on side of the indoor unit. (Fig. 1-27) CZ-26BCU1U CZ-42BCU1U ho /8 ø1 4- Type 2-3/8 Air-intake plenum le Air-intake plenum (including Duct connection box and flange) are attached to the indoor unit when used to take fresh outdoor air.
1. Specifications (d) Installing the ceiling panel Duct connection flange Attach the ceiling panel to the air-intake plenum. Drawing the panel downwards sets the panel in position temporarily with the panel catch (at 2 locations). Duct connection box Installation screws Remove the socket cover of the air-intake plenum and pass the 8P sockets through it. (Fix the panel lead wire to air-intake plenum side clamper.) (M4xL1/2”, 4pcs.
1. Specifications Wall Mounted Type (K1 Type) 6-10. Removing the Wall Fixture from the Unit Remove the set screws and take off the rear panel. (Fig. 1-30) NOTE Set screws for transportation only Fig. 1-30 Tubing can be extended in 3 directions as shown in Fig. 1-31. Select the direction that provides the shortest run to the outside unit. Right-rear tubing (recommended) Left-rear tubling 6-11.
1. Specifications 6-12. Installing the Rear Panel on the Wall Be sure to confirm that the wall is strong enough to suspend the unit. See either Item a) or b) below depending on the wall type. a) If Wooden Wall (1) Attach the rear panel to the wall with the 10 screws provided. (Fig. 1-36) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use toggle bolts to go through the holes on the panel or drill 3/16" dia.
1. Specifications 6-13. Removing the Grille to Install the Indoor Unit Grille Air-intake grille Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps given below: How to remove the grille (1) Set the 2 flaps in the horizontal position. Fig. 1-39a (2) Unscrew the 3 screws. (Fig. 1-39a) Air-intake grille (3) Remove the grille. (a) Hold both corners of the air-intake grille, then pull out and up to open. (Fig.
1. Specifications 6-15. Wiring Instructions General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) To prevent possible hazards from insulation failure, the unit must be grounded.
1. Specifications Cover 6-17. Shaping the Tubing Refrigerant tubing (1) Shape the refrigerant tubing so that it can easily go into the hole. (Fig. 1-45) (2) Push the wiring, refrigerant tubing and drain hose through the hole in the wall. Adjust the indoor unit so it is securely seated on the wall fixture. Inter-unit wiring Drain hose (3) Carefully bend the tubing (if necessary) to run along the wall in the direction of the outdoor unit and then insulate to the end of the fittings.
1. Specifications Front face Ceiling Type (T1 Type) 6-19. Suspending the Indoor Unit (1) Place the full-scale diagram (supplied) on the ceiling at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 1-50). Rear Full-scale diagram Fig. 1-50 NOTE Hole-in-anchor Hole-in-plug Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humidity.
1. Specifications (5) Before suspending the indoor unit, remove the 2 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 1-54. Then remove both side panels sliding them along the unit toward the front after removing the two screws which fix them. (Fig. 1-55) Pull out the air-Intake grille pushing claws of the hinges Screw Hinge Latch de Sli (6) Preparation for suspending the indoor unit.
Approx. 1 inch 1. Specifications (7) Suspend the indoor unit as follows. (a) Mount a washer and two hexagonal nuts on each suspension bolt as shown in Fig. 1-58. Ceiling surface (b) Lift the indoor unit with a lifting machine to the ceiling surface, and place it on the washers through the notches, to fix it in place. (Fig. 1-59) Washer (supplied) Nut (field supply) Suspension bolt Fig. 1-58 (c) Tighten the two hexagonal nuts on each suspension bolt to suspend the indoor unit as shown in Fig. 1-60.
1. Specifications 6-20. Duct for Fresh Air Duct connection port (Knock-out hole) There is a duct connection port (knock-out hole) at the right-rear on the panel top of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by knocking it out and connect the duct to the indoor unit through the connection port. (Fig.
1. Specifications 6-22. Required Minimum Space for Installation and Service min. 9-27/32 Electrical component box Inspection access 17-23/32 × 17-23/32 Indoor Unit Refrigerant tubing min. 25-19/32 min. 15-3/4 This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below. The minimum space for installation and service is shown in Fig. 1-67 and Table 1-7.
1. Specifications 6-23. Suspending the Indoor Unit Hole-in-anchor Hole-in-plug Concrete Insert Depending on the ceiling type: • Insert suspension bolts as shown in Fig. 1-69 or • Use existing ceiling supports or construct a suitable support as shown in Fig. 1-70. Suspension bolt (M10 or 3/8") (field supply) WARNING 1 It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit.
1. Specifications Fig. 1-73 shows an example of installation. Bolt anchor Air outlet duct Suspension bolt Air-intake duct Air-outlet grille Ceiling material Indoor unit Air-intake grille Fig. 1-73 1 6-24. Installing the Drain Piping (1) Prepare standard hard PVC pipe for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. When doing this, leave a gap between the drain socket of the unit and the PVC pipe to allow the drainage to be checked.
1. Specifications Air bleeder CAUTION Do not install an air bleeder tube as this may cause water to spray from the drain pipe outlet. (Fig. 1-76) Not good If it is necessary to increase the height of the drain pipe, the section directly after the connection port can be raised a maximum of 19-11/16". Do not raise it any higher than 19-11/16", as this could result in water leaks. (Fig. 1-77) Fig. 1-76 11-13/16" or less Do not install the pipe with an upward gradient from the connection port.
1. Specifications 6-26. Increasing the Fan Speed Electrical component box If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: Booster cable Fan motor Booster cable Fan motor socket (At shipment) (Booster cable installed) Fig. 1-80 (1) Remove 4 screws on the electrical component box and remove the cover plate.
1. Specifications 6-27. When Installing the Indoor Unit Confirm that the indoor unit should be installed in a horizontal position. Use the level gauge or vinyl tube and check every four corner of the unit is in horizontal. If the air outlet duct flange is positioned with downward gradient, there is in danger of water splash or drainage. Also, dust may sometimes be contaminated inside the drain pan caused by the residual drain water.
1. Specifications SUPPLEMENT ON DRAIN PIPING Checkpoint after installation After installation of indoor and outdoor units, panels and electrical wiring, check the following items. Checkpoint 1 Symptom Make sure whether indoor and outdoor units are correctly installed. Remark Fall, vibration, noise 2 Make sure whether gas leakage is tested. 3 Check No cooling, no heating Make sure whether insulation is completed.
1. Specifications 7. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER IMPORTANT When using this air conditioner with the wireless remote controller it may sometimes be impossible to change the operation modes while other indoor unit is running. When this happens, a double beep tone sounds, the (operation lamp) lights up, and the (Timer lamp) and (Standby lamp) blink alternately. Operation is the same even during (AUTO mode) automatic cooling or heating.
1. Specifications 7-2. Room Temperature Sensor Setting The room temperature sensors are built into the indoor unit and the wireless remote controller. Either of these room temperature sensors can operate. The system is shipped from the factory set to the indoor unit sensor. To switch to the remote control sensor, press the sensor switching button located inside the remote control cover and check that A/C SENSOR on the LCD display panel goes out.
1. Specifications 4-Way Cassette Type (U1 Type) Air intake grille 7-5. Indicator Section Installation Mark section (indicator section) Remove the ceiling panel and indicator cover and install the indicator section. (1) Remove the ceiling panel. (2) Remove the corner cover behind the mark section. (3 screws) (3) Remove the mark section inside the ceiling panel. (2 screws) (4) Install the indicator section in the location where the mark section was attached.
1. Specifications Ceiling Type (T1 Type) 7-7. Indicator Section Installation Remove the side panel to install the indicator section. (Fig. 1-91) Indicator section Indicator section Cover B (Not used when the indicator section is installed.) (1) Remove the side panel. Open the air intake grille, remove the screw at one place and then remove the side panel by sliding it toward the front (arrow direction). (2) Remove cover A and cover B.
1. Specifications 7-9. Electrical Wiring Signal receiving unit Indoor PCB 1 WL 2 Operating controller W2 CN2 (0.7 ft.) CN1 BLU W1 (4.3 ft.) YEL PNK WHT RED BLK GRY BLK W3 Indicator section (4.3 ft.) CN1 BLU YEL PNK RED GRY BLK Relay connector Fig. 1-93 Connection method (1) Connect W1 to the indoor PCB WL connector. (2) Connect W3 from the indicator section with W2 from the operating controller using the relay connector. 7-10.
1. Specifications 7-11. Misoperation Alarm Indicators Alarm indicator lamps on the indoor unit indicate the error cause if the air conditioner fails to operate upon being switched on. The possible alarm indications are given in Table 1-9. Fig. 1-95 shows the location of the alarm lamps on the indoor unit. (See Table 1-9 and Fig. 1-95.) Table 1-9 Alarm (OPERATION lamp) (TIMER lamp) Cause of Trouble (STANDBY lamp) S.C. errors* between the indoor unit’s controller (PCB) and the remote controller.
1. Specifications CAUTION If the signal receiving unit is installed near a rapid-start or inverter type fluorescent lamp (neither one uses glow lamps), it may be impossible to receive signals from the wireless remote controller. To avoid signal interference from fluorescent lamps, install the receiving unit at least 6.6 ft. away from the lamps and install at a location where wireless remote controller signals can be received when the fluorescent lamps are on. 7-12.
1. Specifications When using the signal receiving unit on a wall with the front exposed, choose a wall surface that the signal receiving unit can be mounted on. Run the remote con cable through a notch in the upper case. (1) Insert a flathead screwdriver into the slot on the lower side of the signal receiving unit and pry off the back case.
1. Specifications 7-13. Electrical Wiring CAUTION Be sure to do the wiring correctly (incorrect wiring will damage the equipment). Recommended wire diameter and allowable length for signal receiving unit wiring and its branch wiring: AWG #18, MAX 1,300 ft. Terminal board for indoor unit remote control wiring 1 2 WHT 1 BLK 2 Signal receiving unit Wire from signal receiving unit Connection Signal receiving unit wiring (field supply) Wire joint (2 pcs.
1. Specifications 7-15. Misoperation Alarm Indicators A blinking lamp for other than the signal receiving unit filter shows that a problem has occurred in the unit, so make an inspection. (Refer to servicing information in the service manual, etc.) Also, if wired remote controller and dedicated service check lines (CV6380230938: service use) are available, then detailed error information can be obtained by connecting to the service connector as shown in the drawing.
1. Specifications 7-16. Basic Wiring Diagram In case of using shielded wires for inter-unit control wiring, ground the shield on one side. (Fig. 1-109) Otherwise misoperation because of electrical noise may occur. Be sure to do the wiring correctly (incorrect wiring will damage the equipment). CAUTION Remote Controller Shielded wire 1 2 Ground Wire joint 1 2 Fig. 1-109 Indoor unit No.
1. Specifications 7-17. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a signal receiving unit (main unit). In this case, a signal receiving unit can be connected at any indoor unit. Wiring procedure Wire according to the diagram at left: Address setting is executed automatically when the outdoor unit is turned on.
1. Specifications 7-18. Wiring System Diagram for Multiple Remote Controllers When installing multiple remote controllers This multiple system is used for operating the unit(s) at different positions. (A maximum of 2 signal receiving units can be installed.) Setting method To execute this control, make the setting according to the following procedure. (1) Of the two installed signal receiving units, make one the main signal receiving unit (factory-shipped state).
1. Specifications 7-19. Test Run Procedure Wall mounted Type (K1 Type) Check the “Check Items Before the Test Run.” (Item 7-20) Verify the combination (wiring) of indoor and outdoor units. Set the indoor unit controller to “TEST.” Is operation possible? NO (Item 7-21-3) Check using the Diagnosis function table. (Refer to 7-24) Note: Check the indoor-side drainage. YES 1 Return the indoor unit controller to “NORM.” (Item 7-21-3) 7-20.
1. Specifications 7-21. Preparing for the Test Run 7-21-1. Changing the room temperature sensor Room temperature sensors are installed inside the indoor unit and the wireless remote controller. Either room temperature sensor can be used. When “Unit Sensor” is indicated on the wireless remote controller’s LCD, the indoor unit sensor is operating as the room temperature sensor. To change to the remote control sensor, open the remote control cover and press the SENSOR button once.
1. Specifications 7-22. Precautions Request that the customer be present at the time the test run is performed. Explain the Operating Instructions to the customer, and then have the customer actually operate the system. Be sure to pass the manual and warranty certificate to the customer. Verify that the AC 208 / 230 V wiring is not connected to the terminal plate which is used to connect the inter-unit control wiring. * If AC 208 / 230 V is accidentally applied to this terminal plate, the fuse (0.
1. Specifications 7-23. When Setting Indoor Unit Control PCB Switch for Wall Mounted Indoor Unit When using both the wired and wireless remote controller, refer to the procedure below. If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.) This setting is not necessary for the case of using wireless remote controller only. The slide switch setting at the time of factory shipment for model K1 type is “B.
SM830203-01_PAC-i_US-letter.indb117 117 Operating lamp Nothing is displayed P 0 9 displayed L 0 7 displayed L 0 2 displayed L 1 3 displayed P 0 5 displayed E 2 0 displayed E 1 6 displayed E 1 5 displayed E 0 6 displayed E 0 4 displayed E 1 4 displayed E 0 9 displayed Timer lamp and Standby lamp are blinking alternately. Both the Operation lamp and Standby lamp are blinking together. Operation lamp and Standby lamp are blinking alternately. Standby lamp is blinking.
1. Specifications 8. HOW TO INSTALL THE TIMER WIRED REMOTE CONTROLLER NOTE Refer to the Instraction Manual attaehed to the Timer Remote Controller. 1-13. HOW TO PROCESS TUBING Deburring The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. After Before 1.
1. Specifications Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 1-113) (3) For proper connection, align the union tube and flare tube straight with each other, then screw on the flare nut lightly at first to obtain a smooth match.
1. Specifications Do not use a spanner to tighten the valve stem caps. Doing so may damage the valves. Depending on the installation conditions, applying excessive torque may cause the nuts to crack. Packed valve Charging port Valve stem Precautions for Packed Valve Operation If the packed valve is left for a long time with the valve stem cap removed, refrigerant will leak from the valve. Therefore, do not leave the valve stem cap removed. Use a torque wrench to securely tighten the valve stem cap.
1. Specifications 4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing. Inter-unit control wiring (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
1. Specifications 1-14. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Manifold gauge Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below.
1. Specifications (3) Pressurize the system up to 4.15 MPa (42 kgf/cm2G) with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 4.15 MPa (42 kgf/cm2G). Then, test for leaks with liquid soap. CAUTION Manifold valve Pressure gauge Lo Hi To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Specifications Manifold valve 3. Charging Additional Refrigerant Charging additional refrigerant (calculated from the liquid tube length as shown in Section "1-12. Installation Instructions, 1. Tubing Size, Table 1-2 Tubing Data for Models", Amount of additional refrigerant charge) using the liquid tube service valve. (Fig. 1-126) Pressure gauge Lo Hi Valve Use a balance to measure the refrigerant accurately.
2. PROCESSES AND FUNCTIONS 2-1 2-2 2-3 2-4 2-5 2-6 Room Temperature Control .......................................................................................... 2-2 Cold Draft Prevention (Heating Cycle) ........................................................................ 2-4 Automatic Fan Speed (Indoor Unit) ............................................................................. 2-5 Control Functions ...........................................................................................
2. Processes and functions 2-1 Room Temperature Control The unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the heating cycle.
2. Processes and functions (B) Heating THERMO. ON REMOTE CONTROL SENSOR (Only for wireless remote controller) SET. +2 °F SETTING TEMP. SET. –2 °F THERMO. ON THERMO. OFF THERMO. OFF THERMO. ON THERMO. OFF BODY SENSOR THERMO. ON THERMO. OFF THERMO. ON THERMO. ON +2°F SET TEMP.+7 °F SHIFT –2°F SET TEMP.
2. Processes and functions 2-2 Cold Draft Prevention (Heating Cycle) The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF. This condition occurs in the following 3 cases: • During Thermo OFF (refer to 2-1 B.
2. Processes and functions 2-3 Automatic Fan Speed (Indoor Unit) By pressing the FAN SPEED button on the remote controller, the fan speed can be set at one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed will be automatically adjusted to the room temperature as the two charts shown below. (A) Cooling ROOM TEMP. (deg) +3 +2 +1 SET TEMP. INDOOR FAN SPEED H M L M H H : High L : Low M : Middle 1923_M_S Fig.
2. Processes and functions 2-4 Control Functions Electronic control valve control Opening of the electronic control valve is controlled so that the appropriate operating conditions are maintained, based on the signal from each sensor (discharge temperature [TD], intake temperature [TS], outdoor heat exchanger temperature [C1], and indoor heat exchanger temperature [E1, E2]).
2. Processes and functions Overcurrent protection control (1) If the overcurrent protection circuit detects abnormal current, the compressor is stopped. (Error count = 1.) The compressor then restarts after 3 minutes. (2) If compressor start/stop is repeated 4 times (error count = 4), alarm "P26", "P29" or "H01" (count = 2 in this case only) occurs. Operation stops and does not restart.
2. Processes and functions Defrost control Defrost control Defrost sequence Heating operation (25-minute mask) 1 Frost detection Defrost start (reverse cycle defrost) • Defrost in progress • • • • 2 Defrost cancel Operating frequency: 61.8 Hz Outdoor unit fan: OFF Electronic control valve: step 300 4-way valve: OFF Indoor unit fan: OFF 3 Start-up operation (1) Frost detection 1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start) 2 2.
2.
2. Processes and functions 2-6 Outdoor Unit Control PCB (CR-CH4272R) (1) Explanation of Functions S001 Push-button switch (black): Automatic address setting switch • If the system address switch (S002: set to 0 at time of shipment) setting is other than "0" (central control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
2. Processes and functions Terminal plug (CN015) 3P plug (black): Terminal plug for the communications line • At the time of shipment from the factory, the short-circuiting socket (2P, black) is installed between pins 1 and 2 on the terminal plug (terminal = yes). • When central control is used for multiple systems, leave the short-circuiting socket in place only on the outdoor unit with a system address of 1. At all other outdoor units (other than unit No.
SM830203-01_PAC-i_US-letter.
3. ELECTRICAL DATA 3-1 Indoor Units................................................................................................................... 3-2 3-2 Outdoor Units.............................................................................................................. 3 -10 3-1 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-1 Indoor Units 4-Way Cassette Type : S-26PU1U6, S-36PU1U6, S-42PU1U6 3-2 SM830203-00_PAC-i_US-letter.
3. Electrical data 4-Way Cassette Type : S-26PU1U6, S-36PU1U6, S-42PU1U6 3-3 SM830203-00_PAC-i_US-letter.
3. Electrical data Wall Mounted Type : S-26PK1U6 3-4 SM830203-00_PAC-i_US-letter.
3. Electrical data Wall Mounted Type : S-26PK1U6 3-5 SM830203-00_PAC-i_US-letter.
3. Electrical data Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6 3-6 SM830203-00_PAC-i_US-letter.
3. Electrical data Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6 3-7 SM830203-00_PAC-i_US-letter.
3. Electrical data Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6 3-8 SM830203-00_PAC-i_US-letter.
3. Electrical data Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6 3-9 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-26PE1U6 3-10 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-26PE1U6 3-11 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-26PS1U6 3-12 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-26PS1U6 3-13 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-36PE1U6 3-14 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-36PE1U6 3-15 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-36PS1U6 3-16 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-36PS1U6 3-17 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-42PE1U6 3-18 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-42PE1U6 3-19 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-42PS1U6 3-20 SM830203-00_PAC-i_US-letter.
3. Electrical data 3-2 Outdoor Units U-42PS1U6 3-21 SM830203-00_PAC-i_US-letter.
SM830203-00_PAC-i_US-letter.
4. SERVICE PROCEDURES 4-1. Meaning of Alarm Messages......................................................................................... 4-2 4-2. Symptoms and Parts to Inspect ................................................................................... 4-5 4-3. Details of Alarm Messages ...........................................................................................4-8 4-4. Table of Thermistor Characteristics ............................................................................
4. Service procedures 4-1.
4.
4. Service procedures (2) LED Indicator Messages on Outdoor Control PCB LED 1 LED 2 Power ON sequence 1. No communication from indoor units in system Remarks If it is not possible to advance to 3, repeats 1 → 2. At 3, changes to normal control. 2. Communication received from 1 or more indoor units in system 3. Regular communication OK (Capacity and unit quantity match) Normal operation Displayed during automatic address setting 1 and initial communication.
4. Service procedures 4-2. Symptoms and Parts to Inspect Remote controller alarm display Alarm contents Judgment condition Clear condition Judgment and correction Abnormal discharge temperature • Discharge temp. detected at or above the specified value. High pressure switch is activated. Compressor motor thermal protector is activated. Stops when temp. exceeds 232 ˚F. Recovery at restart Stops when pressure exceeds 600 psi. Stops when temp. exceeds 230 ˚F. Recovery at restart 1.
4. Service procedures Remote controller alarm display Alarm contents P29 Current detection circuit trouble • AC current value is high even when compressor is stopped. Compressor motor output trouble, Inverter compressor trouble, MDC trouble Clear condition Judgment and correction Inverter stops after alarm is detected. Alarm is output when inverter stops (pre-trip) consecutively 4 times. Recovery at restart 1. Stops immediately when restarted. • Layer short in the compressor 2.
4. Service procedures Remote controller alarm display Alarm contents Judgment condition Clear condition Judgment and correction Recovery at power reset 1. Check EEPROM (IC007). 2. Check outdoor unit control PCB. F31 EEPROM trouble L02 Indoor unit judges that type Mismatch of indoor and outdoor unit types does not match outdoor unit type. (Espacio, Multi ) Recovery at power reset 1. Check indoor unit EEPROM. 2. Check indoor unit control PCB.
4. Service procedures 4-3. Details of Alarm Messages (1) [Alarm “P29”] (MDC trouble) Input power detection circuit trouble Compressor does not run. Breakdown Motor current detection circuit trouble Is power OK? No Correct power line. Yes Is current detection circuit wiring OK? Are wiring and connector connections OK? No Check and correct wiring. No Check and correct wiring. Yes Is compressor OK? No Yes Ground fault? Yes Coil resistor short circuit? Coil open circuit? Replace compressor.
4. Service procedures (2) [Alarm “P26”] HIC PCB trouble) IGBT short-circuit protection on inverter control (IPDU) PCB Is power OK? No Correct power line. Yes Are circuit wiring, connector connections, and reactor connections OK? No Correct. Yes Has filter PCB RY001 or RY002 relay activated? No Yes Disconnect U.V.W. output terminal on HIC PCB and start operation. Does alarm “P26” occur? Has filter PCB AC fuse blown? Yes Replace filter PCB. No No Replace HIC PCB.
4. Service procedures HIC-CH2672R (26, 36 Type) HIC-CH4872R (42 Type) Resistance Between terminals 4 (3) [Alarm “E31”] (communications trouble within unit) Resistance HIC + HIC – 200 kΩ or more HIC + U 300 kΩ or more HIC + V 300 kΩ or more HIC + W 300 kΩ or more HIC – U 200 kΩ or more HIC – V 200 kΩ or more HIC – W 200 kΩ or more IGBT short-circuit protection Is “E31” displayed even after the power voltage is reset? No Normal Yes Replace outdoor unit control PCB.
4. Service procedures (4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB? No Correct the connector connections. Yes Disconnect connectors CN003 and CN004 from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily? No Yes Outdoor unit fan motor coil resistance is OK if it is as shown below. * Disconnect connector CN004 and measure on the plug side.
4. Service procedures Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Are connectors CN020, 021, 022, 023, and 024 (TD, TO, C1, C2, and TS sensors) connected correctly to the outdoor unit control PCB? No Correct the connector connections. Yes Are the TD, TO, C1, C2, and TS sensor resistance* characteristics OK? No Replace the TD, TO, C1, C2, or TS sensor. * Refer to “4-4. Table of Thermistor Characteristics.” Yes Check the outdoor unit control PCB. Replace if PCB has failed.
4. Service procedures Sensor Temperature Display Function (Displayed both when operating and stopped) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. (1) Press and hold the button and button simultaneously for 4 seconds or longer. (2) Unit No. X-X (main unit No.), item code XX (sensor address), and service monitor 00XX (sensor temperature) appear on the remote controller LCD. (See figure.
4. Service procedures Check Pin Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below. 1. Thermistor checks The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2. Check results Thermistor Normal Discharge temp. (TD) LED 1 lit Outdoor air temp. (TO) LED 2 lit Heat exchanger temp. (C1) LED 1 lit Abnormal LED 1 and 2 OFF Heat exchanger temp.
5. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 5-1. Overview ......................................................................................................................... 5-2 5-2. Functions ....................................................................................................................... 5-2 5-3. Normal Display Operations and Functions ................................................................. 5-3 5-4.
5. Outdoor unit maintenance remote control 5-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM settings.
5. Outdoor unit maintenance remote control 5-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below.
5. Outdoor unit maintenance remote control • Display (functions) Use the temperature setting and Item code buttons to change the item code. Display contents Remarks 00 (1) Outdoor unit alarm contents (code): OFF when normal Blinking 8-alarm code display at pre-trip, LED (2) At initial status 01 No. of indoor units connected in that refrigerant system 02 Unit. Nos.
5. Outdoor unit maintenance remote control *2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( colon. ) display and the Display for unit Nos. 1 – 20 Not lit Not lit 1 Not lit 6 3 8 4 2 18 14 12 5 19 17 10 15 Lit Meaning of display colon 16 13 9 7 Lit Not lit 11 20 Lit — Lit — — — is not displayed. Display for unit Nos.
5. Outdoor unit maintenance remote control 5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press the button and select the indoor unit to monitor.
5. Outdoor unit maintenance remote control 5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History * * Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. (1) Press and hold the button and button simultaneously for 4 seconds or longer to change to outdoor unit alarm history mode.
5.
5. Outdoor unit maintenance remote control Setting mode 2 (1) Press and hold the seconds or longer. button, button, and button simultaneously for 4 (2) Use the temperature setting and buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time and buttons to change the setting data. To confirm the changed setting data, press the button. (At this time, “Setting” stops blinking and remains lit.
5.
6. TEST RUN 6-1. Preparing for Test Run ............................................................................................... 6-2 6-2. Caution........................................................................................................................ 6-3 6-3. Test Run Procedure .................................................................................................... 6-3 6-4. Items to Check Before the Test Run ..................................................................
6. Test run 6. TEST RUN 6-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. ON (Power must be turned ON at least 5 hours before attempting test run) (2) The control wiring is correctly connected and all electrical connections are tight. (3) The protective spacers for the compressor used for transportation have been removed. If not, remove them now.
6. Test run U1, K1, T1, F1 Type 6-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used. This test run manual describes primarily the procedure when using the wired remote controller. 6-3.
6. Test run 6-4. Items to Check Before the Test Run (1) Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. (2) Fully open the closed valves on the liquid tube and gas tube sides. 6-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer. Then press the button. • “TEST” appears in the LCD display during the test run. • Temperature control is not possible when test run mode is engaged.
SM830203-01_PAC-i_US-letter.indb5 5 Operating lamp Nothing is displayed Indoor unit receiver lamp P 0 9 displayed L 0 7 displayed L 0 2 displayed L 1 3 displayed P 0 5 displayed E 2 0 displayed E 1 6 displayed E 1 5 displayed E 0 6 displayed E 0 4 displayed E 1 4 displayed E 0 9 displayed Timer lamp and Standby lamp are blinking alternately. Both the Operation lamp and Standby lamp are blinking together. Operation lamp and Standby lamp are blinking alternately. Standby lamp is blinking.
6. Test run 6-8. Examples of Wiring Diagrams Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) System address rotary switch (Set to “0” at the time of shipment.) 0 Outdoor unit L1 L2 2 G U1 U2 Inter-unit power line 230 / 208 V, 60 Hz 1 Ground Power supply Single-phase 230 / 208 V 1 Indoor unit 2 U1 U2 RC WHT Remote controller wiring (Field supply) BLK 12 (Optional) Wired remote controller Fig.
6. Test run Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system A maximum of 8 indoor units can be connected to 1 remote controller. Set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to “Setting the system addresses” on next page.) (Set using the system address rotary switch on the outdoor unit control PCB.
6. Test run Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) Outdoorunit control PCB 3 – 5HP System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address 10s digit and 20s digit DIP switch System address rotary switch 0 Automatic address button (black) System address 10s 20s DIPswitch ON ON 1 2 Terminal plug (black) OFF Fig. 6-7 System address No.
6. Test run Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed.
201201 SM830203-01_PAC-i_US-letter.