Outback Power Operator’s Manual
Specifications
64 900-0145-01-01 Rev A
Table 12 Electrical Specifications for Radian Models
Specification
GS7048E
GS3548E
DC Input Maximum Current (surge) 406.5 Adc 203.3 Adc
DC Input Maximum Current (short-circuit) 8975 Adc 4488 Adc
Battery Charger Maximum AC Input 30 Aac at 230 Vac 15 Aac at 230 Vac
Battery Charger Maximum DC Output 100 Adc 50 adc
DC Output Voltage Range (charging) 44 to 68 Vdc 44 to 68 Vdc
Auxiliary Output 0.7 Adc at 12 Vdc 0.7 Adc at 12 Vdc
Auxiliary Relay 10 A at 250 Vac or 30 Vdc 10 A at 250 Vac or 30 Vdc
Mechanical Specifications
Table 13 Mechanical Specifications for Radian Models
Specification
GS7048E
GS3548E
Inverter Dimensions (H x W x D)
71.1 x 40.6 x 22.2 cm
(28 x 16 x 8.75")
71.1 x 40.6 x 22.2 cm
(28 x 16 x 8.75")
Shipping Dimensions (H x W x L)
36.8 x 53.3 x 87.6 cm
(14.5 x 21 x 34.5")
36.8 x 53.3 x 87.6 cm
(14.5 x 21 x 34.5")
Inverter Weight 56.8 kg (125 lb) 37.2 kg (82 lb)
Shipping Weight 63.5 kg (140 lb) 42.6 kg (94 lb)
Accessory Ports
RJ11 (batt temp) and
RJ45 (remote)
RJ11 (batt temp) and
RJ45 (remote)
Non-volatile Memory Yes Yes
Neutral-Ground Bond Switching No No
Chassis Type Vented Vented
Environmental Specifications
Table 14 Environmental Specifications for Radian Models
Specification
Value
Rated Temperature Range (meets component specifications; however, please note
that the inverter output wattage is derated above 25°C)
–20°C to 50°C ( –4°F to 122°F)
Operational Temperature Range (functions, but does not necessarily meet all
component specifications)
–40°C to 60°C (–40°F to 140°F)
Storage Temperature Range –40°C to 60°C (–40°F to 140°F)
IP (Ingress Protection) Rating of Enclosure IP20
Environmental Category Indoor unconditioned
Wet Locations Classification Wet locations: No
Relative Humidity Rating 93%
Pollution Degree Classification PD 2
Maximum Altitude Rating 2000 m (6561’)
Overvoltage Category (AC Input) 3