Installation Instructions
900-0126-01-00 REV A 1
GS-IOB-120/240VAC
Input/Output/Bypass Assembly
Installation Instructions
Purpose
This document provides information on how to install the Input/Output/Bypass
Assembly needed for a 120/240 Vac configuration using an OutBack GSLC
(GS Load Center) enclosure.
This product allows manual switching between a single Radian Series
Inverter/Charger and an AC source, facilitating maintenance and power
continuity. It is intended to be installed within the GSLC or one of its variants.
Scope
This document covers how to install the input, output, and bypass circuit
breakers and mechanical interlock onto the GSLC.
Wiring requirements are
site-specific and will vary by installation.
Certain steps may be omitted or
altered if they do not apply to a particular installation.
These instructions are for use by qualified personnel who meet all local and
governmental code requirements for licensing and training for the installation of
electrical power systems with AC and DC voltage up to 600 volts.
Requirements
OutBack Power’s GS-IOB-120/240VAC is intended as a component for OutBack
listed UL508A or UL1741 Industrial Control Panels, specifically the GSLC variants.
It is intended for indoor use only. This equipment is to be installed by qualified
personnel only. Refer to the GS Load Center Installation Manual for complete
installation instructions.
Grounding Instructions
The enclosure for the GS-IOB-120/240VAC should be connected to a grounded,
permanent wiring system. The AC and DC circuits are not bonded to the
enclosure chassis. System grounding, when required by the National Electric
Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1, is the
responsibility of the installer. All installations should comply with all national and
local codes and ordinances.
The equipment ground is marked with this symbol: