Owners Installation, Operation, and Safety Manual Remote Dispensing Cabinets Models FR102PH FR302DP FR902DP FR910PM
Table of Contents About This Manual ................................................................................................................................... 2 Safety Information ................................................................................................................................... 3 Locking .................................................................................................................................................... 3 Installation .................
Safety Information WARNING! To ensure safe and proper operation of your equipment, it is critical to read and adhere to all of the following safety warnings and precautions. Improper installation or use of this product can cause serious bodily injury or death! 1) NEVER smoke near the dispenser, or use the dispenser near open flames when dispensing a flammable liquid! Fire can result! 2) A Fill-Rite filter should be used on the dispenser outlet to insure no foreign material is transferred to the fuel tank.
Additionally, the Fill-Rite Cabinet Dispensers require a safety approved pressure relief valve be incorporated into the installation, either as part of the pump or separately at the dispenser itself. To assure proper operation your dispenser cabinet must be secured to a solid mounting surface. Fill-Rite recommends installing Cabinet Dispensers on either the KITWB Mounting Bracket kit, or the KITPD pedestal.
Mechanical Installation 1. Install the pump (if not included) securely to the top of the fuel tank per the instructions included with the pump. 2. Install mounting plate or pedestal as applicable for your installation. Refer to the mounting plate “Tank Mounting” section of the mounting plate instructions. 3. Remove the dispenser cover to allow inside access to the bottom of the dispenser (see bracket / pedestal instructions for specific screw locations). Figure 1 4.
FR102PH Wiring Diagram (110 VAC 60Hz) 6
FR102PH Wiring Diagram (220 VAC 60 Hz) 7
FR302DP Wiring Diagram (110 VAC 60 Hz) Pump Wiring (110 VAC) Intrinsic Safety Barrier Wiring (110 VAC) IMPORTANT! Voltage selector switch on pump must be set to 220 VAC for 220 VAC installations (see pump manual for details). Pump comes from factory set to 110 VAC.
FR302DP Wiring Diagram (220 VAC 60 Hz) WARNING! DO NOT attempt to wire the Intrinsic Safety Barrier or the 900DP meter to 220 VAC in any way. Damage and potential destruction to those components will result. 220 VOLT PUMP WIRING DIAGRAM Pump Wiring (220 VAC) AUX LEAD RATED 1.0 AMP Figure 1 Voltage Selector Switch IMPORTANT! When wired to 220 VAC, the voltage selector switch on the pump end (Figure 1) MUST be switched to the 220 VAC position.
FR902DP Wiring Diagram (110 VAC 60Hz) 10
FR902DP Wiring Diagram (220 VAC 60Hz) 11
FR910PM Wiring Diagram (110 VAC 60Hz) 12
FR910PM Wiring Diagram (220 VAC 60Hz) 13
Plumbing Instructions IMPORTANT! Remote dispensers and tank top pumps must be installed in accordance with all local, state, and national electrical code NEC/ANSI/NFPA 70, NFPA 30, NFPA 30A, and NFPA 395. Your Fill-Rite dispenser cabinet should be installed in a manner that does not use the plumbing to support the cabinet in any way. Safety and Emergency equipment should be installed per local, state, and national plumbing for flammable fuels guidelines.
Typical Pedestal Mount Plumbing 1 6 2 3 4 5 Item 1 2 3 4 5 6 Description Remote Dispenser Cabinet (applicable to FR102PH, FR902DP, FR910PM) 1” Inlet Pipe 1” Shut-Off Valve Safety Breakaway Valve Electrical Conduit (Threaded rigid conduit, sealed fittings, conductor seal) Exterior Cover (Right side shown; left side not shown for clarity of installation) CAUTION! Threaded pipe joints and connections should be sealed with the appropriate sealant or sealant tape to minimize the possibility of leaks.
For accurate measurement and to prevent dispenser damage, dispenser and piping must always be filled with liquid and be free of air. Where applicable, the meter portion of your dispenser should be calibrated per instructions in the meter manual prior to its use. 1. Reset register to “0”. 2. Remove nozzle from holder and turn the power on by lifting the switch handle. 3. Dispenser is ready for use. Insert nozzle into container to be filled and start flow of liquid. Do not exceed 50 PSI of line pressure.
Assembly and Disassembly (cont’d) Access to the internal components is gained by removing the top and side panels. 1. Remove the screws on the front and sides of the cabinet. The screws are located around the perimeter at the top. The front screws pass through the sun visor over the display on metering cabinets. 2. Gently lift the top off of the cabinet and set aside. 3.
FR102PH Dispenser Cabinet Measurements Nozzle Boot Power Switch Nozzle Rest Hose Hook 18
FR302DP and FR902DP Cabinet Measurements Nozzle Boot Power Switch Nozzle Rest Hose Hook Nozzle Boot Power Switch Nozzle Rest Hose Hook 57.
FR910PM Precision Meter Cabinet Dimensions Nozzle Boot Power Switch Nozzle Rest Hose Hook Nozzle Boot Power Switch Nozzle Rest Hose Hook 20 DC001404-000 rev.