Datasheet
A22NE-P
26
A22NE-PD A22NE-P A22E Common Note
Common Accessories and Tools
Specifications
Certified Standard Ratings
• UL508 (File No. E76675), CSA C22.2 No.14
6 A at 240 VAC, 10 A at 120 VAC
• TÜV (EN60947-5-1) - Certified direct opening -
(EN60947-5-5)
AC-15 3 A at 240 VAC
DC-13 4 A at 24 VDC
• CCC (GB14048.5)
AC-15 3 A at 240 VAC
DC-13 4 A at 24 VDC
Applicable Standards
UL1059, UL486E (Push-in Plus Terminal Block Types)
Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a
short-circuit protection device. This fuse is not provided in the
main unit.
Certified Standards
Note: Only models with NC contacts have a direct opening
mechanism.
* UL-certification for CSA C22.2 No. 14 has been obtained.
Ratings
Contacts (Standard Load)
Note: 1. The above ratings were obtained by conducting tests under
the following conditions.
(1) Ambient temperature: 20°±2°C
(2) Ambient humidity: 65±5%
(3) Operating frequency: 20 operations/minute
2. Minimum applicable load: 10 mA at 5 VDC (Resistive load)
The operating range may vary depending on the usage
conditions and type of load.
LED Lamp
Certification
body
Standards File No.
UL *
UL508, C22.2 No.14
E76675
TÜV SÜD
EN60947-5-1
(Certified direct opening),
EN60947-5-5
Consult your OMRON
representative for details.
CQC (CCC) GB14048.5 2017010305959182
Rated
insulation
voltage (V)
Rated carry
current (A)
Rated
voltage
(V)
Rated current (A)
AC15
(Inductive
load)
AC12
(Resistive
load)
DC13
(Inductive
load)
DC12
(Resistive
load)
600 10
24 VAC 10 10
--- ---
120 VAC 6 10
240 VAC 3 6
380 VAC 1.9 2
440 VAC 1.6 2
24 VDC
--- ---
4 8
120 VDC 1.1
2.2
240 VDC 0.55
1.1
Rated voltage Operating voltage Current value
6 VAC/VDC 6 VAC/VDC ± 10% Approx. 11 mA
12 VAC/VDC 12 VAC/VDC ± 10% Approx. 12 mA
24 VAC/VDC 24 VAC/VDC ± 10% Approx. 12 mA
100 VAC 100 VAC ± 10%
Approx. 12 mA110 VAC 110 VAC ± 10%
120 VAC 100 VAC to 130 VAC
200 VAC 200 VAC ± 10%
Approx. 12 mA
220 VAC 220 VAC ± 10%
230 VAC 230 VAC ± 10%
240 VAC 220 VAC to 250 VAC