Specifications

3440-0241 Rev G14
P1
MODEL G-FM3
SUPERVISED FIRE MODULE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
17
TELCO IN 1
TELCO IN 2
PREMISES
PHONE 1
PREMISES
PHONE 2
TELCO
PAN
BELL+
BELL-
BELL PAN+
BELL PW R+
BELL PAN-
BELL PW R-
EARTH GND
COLD
WATER
PIPE
MODEL G-EX
ZONE EXPANDER
MODEL G-EX
ZONE EXPANDER
7
8
9
11
12
10
AUX+
SW AUX+
GND
AUX IN
PGM1
PGM2
GRN
RED
GRY
BRN
RJ 31X
JACK
SUPERVISED PROTECTION ZONES
MAX. ZONE RESISTANCE 1000 OHMS
4
3
2
1
5
6
13
14 15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
AC
AC
DATA
AUX+
CLK
GND
SMOKE -
SMOKE+
BELL -
BELL+
PREM
TIP
RING
RING
TIP
TELCO
1
23 45 67 8
16.5VAC, 20VA
TRANSFORMER
(CONNECT TO 24 HR.
POWER SOURCE)
2AMP
+
_
AUX FUSE
CAUTION:
INCORRECT TERMINAL BLOCK CONNECTION
MAY DAMAGE EQUIPMENT.
YEL
RED
GRN
BLK
COMMOM
COMMOM
COMMOM
COMMOM
12 VOLT
BATT
12VDC
BELL
SEE NOTE 8
SEENOTE18&19
MODEL G-824 Alpha
DIGITAL ALARM COMMUNICATION TRANSMITTER (DACT)
SEE NOTE 11
GND
2.2K
2.2K
2.2K
BLK
RED
_
+
2-WIRE SMOKE
DETECTORS
MAX. 10 UNITS
SEE NOTE 13-15
PIN 5
PIN 4
PIN 1
PIN 8
KEYPAD
MODEL G-KP Alpha
MODEL G-KP
J1
1
2
3
NOTE:
1. MAXIMUM COMBINED POWER AVAILABLE ON 824 CONTROL PANEL
INCLUDING TERMINALS 4, 6, 7, 8, 26, 27, AND 28 IS 750 mA AT 12 VDC.
ALL CIRCUITS ARE POWER LIMITED.
2. USE 2.2 KOHM 1/2 WATT RESISTORS FOR ZONES THAT REQUIRE
EOL(ZONETYPE2,3AND4).
4. THE OPERATING VOLTAGE RANGE FOR SMOKE DETECTOR
TERMINALSIS9.3TO14.8VOLT.
5. ZONE EXPANDER G-EX BOARD IS CONFIGURED AS ZONE TO ZONE 16
WHEN JUMPER J1, J2, AND J3 ARE LEFT OPEN.
THE BOARD IS CONFIGURED AS ZONE 17 TO ZONE 24 WHEN J1, J2 ARE
LEFT OPEN AND J3 IS SHORTED.
6. COMMUNICATION BETWEEN CONTROL PANEL G-EX AND G-FM3 IS
MADE THROUGH 4-WIRE CONNECTIONS AS SHOWN. CABLE ASSEMBLY
IS PROVIDED.
7. PGM1 AND PGM2 ARE OPEN COLLECTOR OUTPUTS THAT GO LOW TO
APPROXIMATELY 2V WHEN ACTIVATED. MAXIMUM CURRENT: 20 mA.
8. BOXED AREA SHOWS PHONE AND BELL CONNECTIONS WHEN G-FM3
IS NOT USED. DISREGARD IF USING G-FM3.
9. REFER TO BATTERY CALCULATION CHART IN INSTALLERS MANUAL
(3440-0241) FOR CORRECT AMP-HOUR BATTERY.
FOR UL FIRE APPLICATIONS USE DUAL BATTERY CABLE (60118)
10. TERMINALS 7 AND 10 MUST BE USED FOR CABINET TAMPER FOR UL
LISTED INSTALLATIONS.
11. CONNECT EARTH GROUND TO RIGHT SIDE MOUNTING SCREW.
FOR UL FIRE APPLICATION DO NOT USE THIS MOUNTING SCREW FOR
EARTH GROUND! INSTEAD CONNECT TERMINALS 13 & 14 OF G-FM3 TO
COLD WATER PIPE AND USE THE ENCLOSED MOUNTING KIT IN G-FM3
(SEE G-FM3 MANUAL FOR INSTRUCTIONS).
12. THE UNIT SHOULD BE TESTED WEEKLY.
3400-0132 REV. G
14. DETECTION SYSTEMS DS250/DS250TH - DETECTOR INDENTIFIER=A
SYSTEM SENSOR 2400/2400TH - DETECTOR INDENTIFIER=A
SENTROL 429C/429CT - DETECTOR INDENTIFIER=510A
SYSTEM SENSOR 2300T-DETECTOR INDENTIFIER=A
15. 2-WIRE SMOKE DETECTOR OF DIFFERENT MODELS CANNOT BE
MIXED AND MATCHED.
16. CONTROL PANEL CANNOT DETECT MORE THAN ONE SMOKE
DETECTOR IN ALARM CONDITIONS.
17. CONTROL PANEL COMPATIBILITY IDENTIFIER NUMBER IS 50150.
18. IF USING EXTERNAL POWER SUPPLY TO DRIVE BELL , CONNECT
12V OR 24V DC, 5AMP MAX UL LISTED POWER SUPPLY.
19. UL LISTED METAL CLAD BOXED TRANSFORMER SHOULD BE USED
FOR NFPA-72 APPLICATIONS.
20. DO NOT CONNECT TO A RECEPTACLE CONTROLLED BY A SWITCH.
UL FILE N0. S1152
APPLICABLE U.L. STANDARDS.
SIGNAL SYSTEMS CONTROL UNIT (UL 864), REF NFPA-72 (1993)
ALSO SUITABLE AS A CENTRAL STATION BURGLARY ALARM
CONTROL UNIT (UL 1610), POLICE CONNECT (UL 365),
THE G-EX MODULES MUST BE MOUNTED IN THE G-824 CCS CONTROL
CABIMET IN ALL INSTALLATIONS MEETING COMMERCIAL CENTRAL
STATION BURGLARY ALARM SYSTEM UL611, UL1610, UL365, AND UL609.
AND LOCAL BURGLAR ALARM SYSTEM CONTROL UNIT (UL 609),
HOUSEHOLD FIRE (UL 985) AND BURGLAR WARNING SYSTEM
CONTROL UNIT (UL 1023), DIGITAL DIALER COMMUNICATOR (UL 1635).
THIS PRODUCT HAS NOT BEEN INVESTIGATED FOR MEDICAL
EMERGENCY, PANIC AND/OR HELP SIGNAL APPLICATIONS.
CONNECT EXTERNAL UL LISTED
POWER SUPPLY IF NEEDED.
(NOTE 17)
TO CONTROL PANEL TERM.28
TO CONTROL PANEL TERM.27
TO CONTROL PANEL TERM.32
TO CONTROL PANEL TERM.31
21. FOR INSTALLATION INSTRUCTIONS SEE INSTALLERS MANUAL,
OPTEX PART NUMBER: 3440-0241 REV G.
13. THIS CONTROL UNIT SHOULD BE CHECKED BY A QUALIFIED TECHNICIAN
AT LEAST EVERY 3 YEARS.
AUX+
SW AUX+
GND
AUX IN
PGM1
PGM2
78910
RF- RM1
RADIO TRANSMITTER
(RADIO APPLICATION SHOWN)
7
12
8
9
10
11
4.7K 1.2K
1
2
J1
J2
J3
3
10
9
7
8
6
5
4
12
11
P2 P1
1
2
J1
J2
J3
3
10
9
7
8
6
5
4
12
11
P2 P1
3. BELL AND 2-WIRE SMOKE ZONES REQUIRE 2.2K OHM
FIRE EOL RESISTORS. OPTEX PART NUMBER 5090-0255.
FIGURE 1