Catalogue

MVZ Multi-Position Air-Handling Unit
I
Heat Pump
(FOR MXZ-C OUTDOOR UNITS)
Model Name Indoor Unit MVZ-A12AA4 MVZ-A18AA4 MVZ-A24AA4 MVZ-A30AA4 MVZ-A36AA4
Cooling *1 Rated Capacity Btu/h 12,000 18,000 24,000 30,000 36,000
Heating at 47° F *2 Rated Capacity Btu/h 13,500 20,000 27,000 34,000 40,000
Power Supply Phase, Cycle, Voltage 1-phase, 60Hz, 208 / 230V
Voltage
Indoor - Outdoor S1-S2 AC 208-230V
Indoor - Outdoor S2-S3 ±24VDC
MCA A 1.0
Fan
Airflow at Cooling/Heating
(Lo-Med-Hi)
CFM 280-340-400 410-497-585 515-625-735 613-744-875 767-931-1095
External Static Pressure *3 In. W.G. 0.30-0.50-0.80
Sound Pressure Level at Cooling/Heating
(Lo-Med-Hi) *1
dB(A) 27-31-35 28-32-36 30-34-38 32-36-40 35-39-43
External Finish Color High-gloss polyester powder coated
Dimension Unit
W: In. 50-1/4 54-1/4
D: In. 17 54-1/4
H: In. 21-5/8
Weight Unit Lbs. 113 141
Refrigerant Type R410A
Refrigerant Pipe
Gas Side O.D. In. 1/2 5/8
Liquid Side O.D. In. 1/4 3/8
Connection Method Indoor/Outdoor Flared/Flared
NOTES: Test conditions are based on AHRI 210/240.
*1. Rating conditions (cooling)-Indoor: D.B. 80º F (26.7º C), W.B. 67º F (19.4º C); Outdoor: D.B. 95º F (35º C), W.B. 75º F (23.9º C).
*2. Rating conditions (heating)-Indoor: D.B. 70º F (21.1º C), W.B. 60º F (15.6º C); Outdoor: D.B. 47º F (8.3º C), W.B. 43º F (6.1º C).
*3. External static pressure is factory set to 0.05" W.G. at factory shipment.
Specifications are subject to change without notice.
LIMITED WARRANTY I Five years parts and seven years compressor.
44 / MITSUBISHI ELECTRIC / M-SERIES / SPECIFICATIONS