Datasheet

45
3
Input device for temperature sensor
Analog control
Input device for
temperature sensor
Platinum resistance thermometer sensor (Pt100) or thermocouple temperature sensors can be connected.
FX3U-4LC type temperature control module, which provides PID control function with auto tuning, can use a function of
intelligent function module to perform temperature control.
List of devices for temperature sensor input
Model
(Number of channels)
Available sensor
Input specications
Isolation
Compatible
CPU module
Number
of
channels
Items Temperature input FX5U FX5UC
FX3U-4LC (4 ch)
Platinum resistance thermometer sensor
Pt100, JPt100, Pt1000
Input
range
[Typical example]
Pt100: -200 to 600°C
Pt1000: -200.0 to 650.0°C
Between internal
cir
cuit and channel:
Isolation
Between inter
nal
cir
cuit and power
supply: Isolation
Between channels:
Isolation
4 ch
Resolution
0.1°C or 1°C
(diers depending on the sensor used)
Thermocouple
K/J/R/S/E/T/B/N/PLII/W5Re/W26Re/U/L type
Input
range
[Typical example]
K type: -200.0 to 1300°C
J type: -200.0 to 1200°C
Resolution
0.1°C or 1°C
(diers depending on the sensor used)
Low voltage input
Input
range
0 to 10 mV DC
0 to 100 mV DC
Resolution 0.5 μV or 5.0 μV
Û
: Connection with FX5U or FX5UC requires FX5-CNV-BUS or FX5-CNV-BUSC.