Datasheet
45
3
Input device for temperature sensor
Analog control
Input device for
temperature sensor
Platinum resistance thermometer sensor (Pt100) or thermocouple temperature sensors can be connected.
FX3U-4LC type temperature control module, which provides PID control function with auto tuning, can use a function of
intelligent function module to perform temperature control.
List of devices for temperature sensor input
Model
(Number of channels)
Available sensor
Input specications
Isolation
Compatible
CPU module
Number
of
channels
Items Temperature input FX5U FX5UC
FX3U-4LC (4 ch)
Platinum resistance thermometer sensor
Pt100, JPt100, Pt1000
Input
range
[Typical example]
Pt100: -200 to 600°C
Pt1000: -200.0 to 650.0°C
Between internal
cir
cuit and channel:
Isolation
Between inter
nal
cir
cuit and power
supply: Isolation
Between channels:
Isolation
4 ch
Resolution
0.1°C or 1°C
(diers depending on the sensor used)
Thermocouple
K/J/R/S/E/T/B/N/PLII/W5Re/W26Re/U/L type
Input
range
[Typical example]
K type: -200.0 to 1300°C
J type: -200.0 to 1200°C
Resolution
0.1°C or 1°C
(diers depending on the sensor used)
Low voltage input
Input
range
0 to 10 mV DC
0 to 100 mV DC
Resolution 0.5 μV or 5.0 μV
Û
: Connection with FX5U or FX5UC requires FX5-CNV-BUS or FX5-CNV-BUSC.