Manual & Installation Guide

Exhaust duct
37
Only use smooth pipes or flexible
duct hoses made from non-
flammable materials for exhaust
ductwork.
To achieve the greatest possible air
extraction with the lowest noise
levels, please note the following:
The diameter of the exhaust duct
should not be less than 6" (150mm).
If flat exhaust ducts are used, the
cross section should not be smaller
than that of the exhaust connector.
The exhaust duct should be as short
and straight as possible.
If elbows are needed, make sure they
have a large radius.
The exhaust duct itself must not be
kinked or compressed.
Make sure that all connections are
secure and airtight.
Remember that any constriction of
the airflow will reduce extraction
performance and increase operating
noise.
If the exhaust duct is to be routed
through an outside wall, we
recommend installing a telescopic
wall vent or a rooftop vent (available
as an optional accessory).
If the exhaust air is to be conducted
into a vent flue, the intake piece must
be aligned with the flow direction of
the flue.
When installing the exhaust duct
horizontally, you must slope it away
from the source by at least ³/₈" per
3'3" (1cm per meter). This ensures
that condensate cannot drain back
into the ventilation hood.
If the exhaust duct is to be routed
through rooms, ceiling space etc., the
temperatures in these different areas
may differ greatly, which means that
the problem of condensation will
need to be addressed. The exhaust
duct will need to be insulated.
Condensate trap
In addition to insulating the exhaust
duct, we recommend installing a
condensate trap to collect and
evaporate any condensate which might
accumulate.
Condensate traps are available for
exhaust ducts with a diameter of
5" (125mm) or 6" (150mm).