Configuration Manual Owner's manual

Command Series Migration to MOD 30ML
Pre-configured PID Ratio with Remote SP
To change the value of the Output Limits (S16, S17):
Open the PID block and open the Output tab. Change the values for the Output Limits
Low and High and Output rangeLow and High.
See figure below:
Figure P6.10.
PID Ratio with
Remote SP
P6- 13