User guide

Remote I/O Modules
PRODUCT DESCRIPTION
1.4 ELECTROMAGNETIC COMPATIBILITY (EMC)
- electrostatic discharge (ESD) according to IEC 801-2 (severity level 3)
- test peak voltage :
at discharge through air 8 kV
at discharge through relay's contact 6 kV
time between two discharges > 1s
number of discharges on each selected point 10
radiated electromagnetic field immunity test according to IEC 801-3
field strength 10 V/m (severity level 3)
frequency range 27 MHz to 1000 MHz
sweep speed 1.5 x 10E-3 decade/s
fast transient burst test (FTT) according to IEC 801-4
interference voltage for :
mains terminals 115/230 V 2 kV
mains terminals 24 V 2 kV
output terminals 24 V 1 kV
output terminals 115/230 V 2 kV
input terminals 24 V 1 kV
input terminals 115/230 V 2 kV
CS 31 bus 2 kV
surge immunity according to IEC 801-5
test voltage for asymmetric coupling common mode
power supply (115/230 VAC) 2 kV
power supply (24 VDC) 1 kV
digital inputs/outputs 1 kV
test voltage for symmetric coupling differential mode
power supply (115/230 VAC) 1 kV
power supply (24 VDC) 0.5 kV
digital inputs/outputs 0.5 kV
4