Setup Instruction Manual

MOD 30ML Operation
APPENDIX A - EVENT CODES
A-15
Table A-2. Event Codes, Description and Action
Block
Type
Codes Full Message Text Description/Action
RIO 4 I/O MISMATCH A configured slot is either empty or the installed
module does not match the slot configuration.
RIO 5 CS-31 BUS COMMUNICATION ERROR There is an error in communication or loss of
communication between the RIO interface
module and the CS-31 bus.
RIO 6 I/O COMMUNICATIONS ERROR An error occurred in communication between
the RIO module and the instrument.
RIO 7 CS-31 DATABASE CHECKSUM ERROR The remote I/O database stored in the interface
module has been declared bad due to a
checksum error.
RIO 8 MODULE EXTENDED ERROR There is an RIO module error.
RSK 0 BLOCK STATE SET TO RUN Information only.
RSK 1 BLOCK STATE SET TO HOLD Information only.
RSK 2 BLOCK STATE SET TO OFF Information only.
RSK 3 BLOCK STATE SET TO DEBUG Information only.
RTI 0 BLOCK STATE SET TO RUN Information only.
RTI 1 BLOCK STATE SET TO HOLD Information only.
RTI 2 BLOCK STATE SET TO OFF Information only.
RTI 3 BLOCK STATE SET TO DEBUG Information only.
RTI 4 CALCULATION ERROR A calculation error (calculation overflow or
divide by zero) has been detected. The block
completes the calculation using some
reasonable value (+ or - maximum value for
overflows and divide by zero), and sets the
output quality bad if Attribute No. 10, Set quality
bad on calculation error? (SETQBAD) is YES.
The diagnostic error clears and the quality is
set back to good when a subsequent execution
of the block performs a successful calculation.
RTTI 0 BLOCK STATE SET TO RUN Information only.
RTTI 1 BLOCK STATE SET TO HOLD Information only.
RTTI 2 BLOCK STATE SET TO OFF Information only.
RTTI 3 BLOCK STATE SET TO DEBUG Information only.
RTTI 4 CALCULATION ERROR A calculation error (calculation overflow or
divide by zero) has been detected. The block
completes the calculation using some
reasonable value (+ or - maximum value for
overflows and divide by zero), and sets the
output quality bad if Attribute No. 10, Set quality
bad on calculation error? (SETQBAD) is YES.
The diagnostic error clears and the quality is
set back to good when a subsequent execution
of the block performs a successful calculation.