Specifications

Engineer’s Menu 1 TS790+ & TS900+ Installation Manual
17 Loud Chime Tones
When programmed as “Yes” the chime
tones are always at full volume. When
programmed as “No” the chime tones are
at the level set by VR1 on the main PCB.
(Default = No)
18 Invert Output 1
When programmed as “Yes” panel output 1
is inverted. When programmed as “No
panel output 1 is normal. (Default = No)
19 Invert Digi Outputs
When programmed as “Yes"” the eight
digicom outputs on the control panel switch
from 0V to +12V when active (+ve applied).
When programmed as “No” the eight
digicom outputs on the control panel switch
from +12V to 0V when active (+ve
removed). (Default = No)
20 On-Line Keypad
When programmed as “Yes" the Menvier
Lineload On-Line Keypad feature is enabled.
When programmed as “No” the Menvier
Lineload On-Line Keypad feature is disabled.
(Default = Yes)
21 Restore Contact ID
When programmed as "Yes" the Contact ID
restore status is transmitted. When
programmed as "No" Contact ID restore is
not transmitted. (Default = Yes)
22 User Authorised
When programmed as “Yes” the Menvier
Lineload software can only write information
to the control panel after the user has
authorised remote communications. When
programmed as “No” the Menvier Lineload
software can write information to the control
panel without user authorisation. (Default =
No)
23 Mimic Alarms and Faults
When programmed as “Yes” any outputs
programmed as the type "Circuit Alarm" will
activate when the relevant circuit is armed
and in alarm or in a fault condition. When
programmed as “No” any outputs
programmed as the type "Circuit Alarm" will
activate when the relevant circuit is in alarm,
whether the circuit is armed or disarmed.
(Default = No)
24 Sounder on Confirm
When programmed as "Yes" the control unit
activates the internal sounders after a
confirmed alarm and any programmed bell
delay. When programmed as "No" the
control unit starts the internal sounders
immediately after an unconfirmed alarm.
(Default = No)
25 Bells on Confirm
When programmed as "Yes" the control unit
activates the external sounders after a
confirmed alarm and any programmed bell
delay. When programmed as "No" the
control unit activates the external bell
immediately after an unconfirmed alarm.
(Default = No)
26 Confirmation After Entry
When programmed as "Yes" the control unit
sends a confirmed alarm if the intruder
activates one or two separate zones after
the entry timer expires. To select between
one or two zones use "27 Entry conf 2 cct"
When programmed as "No" the control unit
disables alarm confirmation when a user
starts the entry timer. Use the "No" option to
comply with DD243:2002 paras 6.4.2, 6.4.3,
6.4.4 and 6.4.6.
(Default = No)
27 Entry Confirmation After 2 circuits
When programmed as "Yes" the control unit
sends a confirmed alarm if an intruder
activates two separate zones after the entry
timer expires. If the control unit is in alarm
before the user starts entry then only one
subsequent zone violation is required.
Note: Select this option if you are installing a
DD243:2002 para 6.4.5 compliant system
and the user must unset the system with a
proximity detector ("Portable ACE").
When programmed as "No" the control unit
sends a confirmed alarm if the intruder
activates one zone after the entry timer
expires. This option does not comply with
DD243:2002.
If you program Confirmation After Entry as
"No" then the setting of this option has no
effect.
28 Confirmation On
When programmed as "Yes" then the
Digicom reports a Channel 3 (005 Intruder)