Datasheet

SPECIFICATION
MODEL
MTBF
DIMENSION
NOTE
PACKING
1. All parameters NOT specially mentioned are measured at rated load and 25 of ambient temperature.
2. Battery fail will only function at UPS mode with battery connected. Every 25 seconds, unit will send out test signal through "Battery Fail" relay contact and
LED indicator once the battery is fail.
3. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
4. Battery charging will be in progress when DC input > battery voltage.
5. DR-UPS40 will be in operation when DC input is applied at the beginning.
FileName:DR-UPS40-SPEC2012-05-14
40A DCUPSModule
DR-UPS40
Features :
DCINPUT/
DCBUS
BATTERY
INPUT/
OUTPUT
OTHERS
ENVIRONMENT
DR-UPS40
DCVOLTAGE(Typ.) Note.5
RATEDCURRENT
VOLTAGERANGE(Typ.)
CURRENTRANGE
CHARGECURRENT(Typ.) Note.4
EXTERNAL BATTERY (Typ.)
RELAY CONTACTRATING(max.)
DCBUSOK
BATTERY FAIL Note.2
BATTERY DISCHARGE
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
VIBRATION
24~29V
40A
21~29V
0~40A
2A
4/7/12AH/24V
30VDC,1A
Relaycontact:ShortwhenDCvoltagebetween21~29V( 3%),relaycontacts
LED(Green):DCBUSOK:light;DCBUSfail:dark
LED(Red):Batteryover-dischargewarningorbatterybroken:light;BatteryOK:dark
Shortwhenbatteryvoltagefallsbelow21.9V( 3%)orbatteryfailureisobservedthroughthebatterytestfunction,relaycontacts
Relaycontact: Shortwhenbatteryindischargecondition,relaycontacts
LED(Yellow):Batterydischarging:light;Batteryisnotdischargingordischargingcurrent<2.0A :dark
-20~+70
20~90%RH
-20~+85 ,10~95%RH
Component:10~500Hz,2G10min./1cycle,60min.eachX, Y,Zaxes;Mounting:CompliancetoIEC600068-2-6
FUNCTION
161.9Khrsmin.MIL-HDBK-217F(25 )
55.5*125.2*100mm(W*H*D)
0.55Kg;20pcs/12Kg/1.29CUFT
SAFETY &
EMC
(Note3)
Battery controller for DIN Rail UPS system
Parallel connection to DC BUS
Suitable for 24V system up to 40A
Installed on DIN Rail TS35 / 7.5 or 15
Built-in battery test function
Battery polarity protection
Relay contact signal output and LED indicator for DC BUS OK,
Battery Fail, and Battery Discharge
Cooling by free air convection
3 years warranty
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
Terminal-Chassis:>100MOhms/500VDC/25 /70%RH
Terminal-Chassis:0.5KVAC,RelayContacts-Terminal:0.5KVAC
CompliancetoEN55022(CISPR22)ClassB, EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8 ,heavyindustrylevel,criteria A,11
EMCIMMUNITY
EMCEMISSION

Summary of content (3 pages)