ME-AGS-N Manual

© 2016 Sensata Technologies 26
Troubleshooting
5.2 Generator Starting/Running Troubleshooting
This section helps troubleshoot the generator system when the
AGS’s STATUS LED illuminates solid red (fault condition), or the
remote control displays a generator autostart fault.
Press the TEST button on the AGS controller, or start the
generator from your remote control.
5.2.1 If the Generator does not Start or Run
If the generator does not start after pressing the AGS’s TEST button:
1. Ensure the green READY indicator on the AGS controller is on
( ashing or solid) to indicate that the AGS is getting power.
2. Check the generator for fuel or for any fault codes, or check
the generator’s operating manual for troubleshooting tips.
3. Ensure the start/stop wiring has not come loose and is correctly
connected for your generator model. A wiring diagram for your
particular brand and model of generator may be available,
check our website:
www.Magnum-Dimensions.com.
4. Your generator may require a higher amperage start signal
than what our AGS relays are rated (approximately 5 amps);
in that case, you need to supply a higher-rated external relay.
5. If the generator tries to start as soon as you initiate a test
(instead of waiting for the initial stop signal before attempting
to start), check the start and stop wire connections (reversed?).
6. Remove the generator start/stop wires from the AGS’s 8–port
terminal. Simulate the AGS relays by physically connecting
the start wires rst to ensure the generator starts and runs.
Then, connect the stop wires and ensure the generator stops.
If the generator does not start or stop as it should, recheck
and troubleshoot the start/stop wiring to the generator.
5.2.2 If the STATUS LED does not go Solid
If the generator is running, but the STATUS LED on the AGS
controller is not on solid, then:
1. Ensure the AGS is not in warm-up (STATUS LED should go
solid once the warm-up period is over).
2. Con rm you are getting the correct gen run sense signal
based on your Gen Type setting.
Info: Refer to the Gen Type Setting section (page 21) and
Table 3-1 (page 22) to determine your Gen Type setting.