PDRYCB300 Installation Manual

Installation manual 15
ENGLISH
CN_WIND
DISPLAY_LED
TEMP_SW
SETTING_SW
CN_OUT
Setting and using method
4. Setting of ‘TEMP_SW’
n When setting the desired temperature of the Dry contact
Module
: When operating the indoor unit using Dry contact module’s desired temperature, set the desired
temperature according to the ‘TEMP_SW’ setting.
If Thermostat priority control mode is disabled, the desired temperature can be reset by other controller
- Use the ‘TEMP_SW’ to set the temperature as shown below.
TEMP
(°C)
'TEMP SW'
setting
Not use Dry Contact
module's Desired
temp function
0
18 19 20 21 22
12345
TEMP
(°C)
'TEMP SW'
setting
23 24 25 26 27 28 29 30
6789ABCD
*. E, F : Reserved