Specification Sheet - LMU36CHV
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
MultiFInverterHeatPumpOutdoorUnit
Performance:
LMU36CHV
NominalCoolingCapacity(Btu/h)
34,000
CoolingPowerInput(kW)
2.46
HeatingPowerInput(kW)
2.74
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB
Indoor:
70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB
Outdoor:
47°FDB/43°FWB
Electrical:
PowerSupply(V¹/H z/Ø)
208‐230/60/1
MOP(A)
25
MCA(A)
17.9
CoolingRatedAmps(A)
15.13
HeatingRatedAmps(A)
15.13
Compressor(A)
11.2
FanMotor
(
A
)
0.73
Piping:
RefrigerantCharge(lbs)
6.18
LiquidLine(in,OD)
1/4x4
VaporLine(in,OD)
3/8x4
MaxTotalPiping²(ft)
246.1
MaxElevationbetweenODUandIDU(ft)
49.2
MaxElevationbetweenIDUandIDU(ft)
24.6
ControlsFeatures:
•Autooperaon
•Autorestartoperaon
•Defrost/Deicing
•Inverter(variable
speedcompressor)
•Built‐inlowambientstandard
downto14F
•Restartdelay (3‐minutes)
•Selfdiagnosis
•Sostart
OperatingRange:
Cooling(°FDB)
14‐118
Heating(°FWB)
‐4‐64
UnitData:
RefrigerantType
R410A
RefrigerantControl
EEV
SoundPressure³(Cool/Heat)±3dB( A)
52/55
NetUnitWeight(lbs)
137
ShippingWeight(lbs)
148
HeatExchangerCoating
GoldFin™
MaxNumberofI ndoorUnits
4
Compressor:
Quantity
1
Type
TwinRotary
Oil/Type
FVC68D
Fan:
Type
Propeller
Quantity
1
FanMotor/Drive
B
rushlessDigitallyControlled/Direct
AirflowRate(CFM)
2119
Notes:
1.Acceptableoperangvoltage:187V‐253V.
2.Pipinglengthsareequivalent.
3.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard19 96.
4.Allpower/communicaoncabletobeminimum18AWG,4‐conductor,stranded,shielded
andmustcomplywithapplicablelocalandnationalcode.
5.Powerwiringcablesizemustcomplywit
htheapplicablelocalandnaonalcode.
6.SeeEngineeringManualforsensibleandlatentcapacies.
7.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
8.Thisdataisrated0abovesealevel,with24.6ofrefrigerantlineanda0level
differencebetweenout
doorandindoorunits.Allcapacitiesarenetwithacombinationratio
between95–105%.
9.RefertotheEngineeringProductDataBookforcombinaoncapacity ta bl es .
10.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
MaxODUtoIDUPiping(ft)
82
PipingLengt h(noadd'lrefrigerant,ft)
98.4
MinNumberofIndoorUnits
2
O
p
tionalAccessories:
PI‐485IntegrationBoard‐PMNFP14A0
ACSmartPremium‐PQCSW421E0A
ACEz‐PQCSZ250S0
MOP‐MaximumOvercurrentProtection MCA‐MinimumCircuitAmpacity
ODU‐OutdoorUnit IDU‐IndoorUnit
PowerDistributionIndicator‐PQNUD1S00
Page1of2
SB‐MultiF‐LMU36CHV‐08‐14
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac .com.
Foracomplet e listof availableaccessories,contactyourLG representative.
NominalHeatingCapacity(Btu/h)
41,000