GENERAL DATA
Multi F MAX Outdoor Unit Electrical Data
Nominal
Tons
Unit Model
No.
Phase Hertz Voltage
Voltage
Range
(Min. to
Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Unit Fan Motor(s)
Indoor
Unit Fan
Motor
kW x Qty. FLA x Qty. FLA
4.0 LMU481HV
1 60 208 -230 187 - 253
32.7 40 1 22.0 2 x 0.12 1.60 x 2 4.0
4.5 LMU541HV 32.7 40 1 22.0 2 x 0.12 1.60 x 2 4.8
5.0 LMU601HV 32.7 40 1 22.0 2 x 0.12 1.60 x 2 5.2
Table 4: LMU481HV, LMU541HV, and LMU601HV Electrical Data.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
IROORZV/DUJHVWPRWRU)/$[6XPRIRWKHUPRWRU
FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.